(Alternating Relay)
Timer Functions
Counting and Switching Functions
OPERATION: Input voltage must be applied before and during operation. The operation begins with
the output (relay or solid state) de-energized. Upon momentary or maintained closure (leading edge
triggered) of the initiate switch S1, the time delay begins. At the end of the time delay, the output
energizes and remains energized. Opening or re-closing S1 during timing has no affect. After the output
transfers, the next closure of S1 starts a new operation. Each time an S1 closure is recognized, the time
delay occurs and then the output transfers, ON to OFF, OFF to ON, ON to OFF. The rst operation will
occur if S1 is closed when input voltage is applied.
RESET: Removing input voltage resets the time delay and the output to the de-energized state.
Function can be applied to ProgramaCube Series: HRPS, KRPS, KSPS
OPERATION: Input voltage must be applied at all times for proper operation. The operation begins
with the output (relay or solid state) de-energized. Closing S1 enables the next alternating operation.
When S1 opens (trailing edge triggered), the time delay begins. At the end of the time delay, the output
energizes and remains energized until S1 is (re-closed and) re-opened. Then the output relay de-energizes
and remains until S1 opens again. Each time S1 opens the time delay occurs and the output transfers.
RESET: Removing input voltage resets the output and the time delay.
See: ARP, HRPS, KRPS
Leading edge ip-op: (ProgramaCube
®
Function F)
Counter with Pulsed Output: (ProgramaCube
®
Function C)
Counter with Interval Output: (ProgramaCube
®
Function CI)
Function Limited to Switch Adjustable ProgramaCubes
®
OPERATION: Input voltage must be applied before and during operation. Each time S1 is closed, a count
is added. When the total number of S1 closures equals the total count selected on the unit, the output
energizes. The output remains energized for the pulse duration specied for the product, and then de-
energizes. If S1 is closed while the output is energized, a count is not added. If S1 is closed when input
voltage is applied, a count is not added.
RESET: The unit automatically resets at the end of each operation. Removing input voltage resets the
output, counter, and pulse delay.
See: HRPU, KSPU, NHPU
Function Limited to Switch Adjustable ProgramaCubes
®
OPERATION: Input voltage must be applied before and during operation. Each time S1 is closed, a count
is added. When the total number of S1 closures equals the total count selected on the unit, the output
energizes and the interval time delay begins. The output de-energizes at the end of the time delay. If
S1 is closed during the time delay, a count is not added. If S1 is closed when input voltage is applied,
a count is not added.
RESET: The counter is reset during the time delay, the unit automatically resets at the end of the interval
time delay. Removing input voltage resets the output, counter, and time delay.
See: HRPU, HRV, HSPZ, KSPU, NHPU
Trailing Edge Flip-Flop
Leading Edge Flip-Flop
Counter with Pulsed Output
Counter with Interval Output
Alternating Relay (Trailing edge ip-op): (ProgramaCube
®
Function FT)
Legend
V = Voltage
R = Reset
S1 = Initiate Switch
Td, TD1, TD2 = Time Delay
NO = Normally Open Contact
NC = Normally Closed Contact
C = Count
P = Pulse Duration
= Undened Time