Site Preparation Considerations
PLEASE
READ: IMPORTANT
To avoid overloading the power management switch and exceeding the electrical
tolerances of your site, it is important that you know the power consumption
requirements of the devices you will be connecting before
attempting an installation of
this product. Most items have their power consumption characteristics printed on the
outside of the device, on the power adapter (if applicable), or in their documentation. If
you are unsure about the power needs of any device you wish to connect to the switch,
contact the manufacturer or your System Administrator.
If you are installing the switch into an existing site and are not altering other
components of your setup (i.e. adding an additional computer), it is likely you will simply
have to concern yourself with the devices you are connecting and not with the electrical
installation of the site itself. If you have experienced power-related problems at the site
previously (i.e. breakers being tripped), you should consult a qualified electrician to
resolve those problems before beginning installation.
If you are installing the switch in a new site and have not been running the devices
you are connecting to the switch together before, you should inventory the requirements
of the devices you are installing and consult a qualified electrician to ensure the electrical
infrastructure will support the combined load of all the devices together without potential
problems.
Note the following considerations when connecting devices to the power management
switch:
1) The load of any single port cannot exceed 6 amps
2) The total load of all connected devices cannot exceed 15 amps
NOTE: Do not connect devices such as UPSes (uninterruptible power supplies),
extension cords, power bars, etc. to any port on the switch. If you wish to use a UPS
solution, plug the power management switch into a UPS of sufficient capacity to handle
the simultaneous load of every
device on the switch. While it does not void the warranty,
the use of a UPS with the power management switch is not supported by StarTech.com.
Installing the Switch and Connecting Devices
1. Place the power management switch near the devices you wish to use, mounting it in
your rack or cabinet, if desired. Connect the female end of the power cord to the
connector on the left hand side of the rear panel, marked POWER IN. Connect the
opposite end to an appropriate power outlet. Ensure the cooling vents on both
sides of the product are unobstructed.