TROUBLESHOOTING THE EFFIKAL DAMPER (continued)
Condition:
Thermostat closed, damper is open fully
STEP 10A TEST FOR 24VAC BETWEEN BLACK AND YELLOW
IF THEN
24VAC is present This is correct – continue to Step 11
24VAC is not present See Step 9B.
Check the harness plug connecting.
Check that cam on shaft rotates with
shaft.
Replace the damper board.
Ensure that cam is secure against end
switch.
Condition:
Damper rotates continuously
STEP 10B ADJUST END SWITCH TO CAM CONTACT
IF THEN
Damper stops in proper position 24 VAC should be open on a call for heat
and close during standby/
Damper does not stop in proper position Replace damper assembly.