OREC:
Recooling function
Adjustment: OFF / ON
Recommended setting: ON
The recooling function is used to cool the tank when the 
maximum tank temperature (S MX) is exceeded, such as when 
the collector cooling function (OCX) is activated and the tank 
may reach 190 °F (emergency shut down of the tank).
When the collector is 5° cooler than the tank the pump will run 
to dump excess heat from the tank in the piping and at the 
solar collector until the tank is cooled to the maximum tank 
temperature setting.
The tube collector function is only needed for systems that use 
vacuum tube solar collectors.
This function is not necessary for this system.
OTC:
Tube collector function
Adjustment: OFF / ON
Recommended setting: OFF
OHQM:
Heat quantity measurement
Adjustment: OFF / ON
Recommended setting: OFF
A Heat quantity measurement is possible for this system 
in  conjunction  with  the  ow  meter.    In  order  for  this  function 
measure the heat gain of the system the optional temperature 
sensor 4 (return ow sensor) must be added and connected to 
the copper pipe between the coil outlet on the tank (marked “to 
pump”) and the solar pump station.
FMAX:
Volume ow in gal/min
Adjustment range: 
0.0 to 20.0 in steps of 0.1
Recommended setting: pump 
station ow meter reading 
converted to (l/min).
For OHQM to give an accurate reading the volume ow readable 
at the owmeter (l/min) must be adjusted in the channel FMAX.
Channel only available when OHQM is active
MEDT:
Type of antifreeze
Adjustment range: 0 to 3
Recommended setting: 1
Channel only available when 
OHQM is active.
For OHQM to give an accurate reading the type of heat transfer 
uid type(antifreeze) must be set in the channel MEDT: 
0: water
1: propylene glycol
2: ethylene glycol
3: Tyfocor ® LS / G – LS
Caution: for this system type only type 1: propylene glycol 
should be selected. Use of any other type of heat transfer uid 
in this system may cause damage to the system or present a 
health hazard
MED%:
Concentration of antifreeze by 
volume %
Adjustment range: 20 to 70%
Recommended setting: 50
The antifreeze concentration by % volume should be entered in 
this channel for OHQM to give an accurate reading. 
Standard system concentration should be a 50% propylene 
glycol and 50% distilled or de-mineralized water. 
Channel only available when OHQM is active.
kWh/MWh:
Heat quantity value shown 
in the kWh and MWh display 
channels. The sum of both 
channels form the total heat 
output.
Channel only available when 
OHQM is active
The total heat quantity value can be reset. When one of the 
heat quantity display channels is selected the symbol   is 
permanently shown in the display. The set button (3) must be 
pressed for approximately 2 seconds in order to go into the 
reset mode for the counter. The display symbol    will be 
ashing and the value for heat quantity will be set to 0. In order 
to nish the reset procedure the set button (3) must be pressed 
in order to conrm.
In order to interrupt the reset procedure no button should be 
pressed for about 5 seconds. The controller will automatically 
return to the indication mode with the previous total.