User Manual
25
HP transfer pump and another hose from the transfer 
pump to the fill valve (d) then open this valve.
23.  Turn on the transfer pump to fill the system with the 
glycol solution and allow to circulate for 15 minutes in 
order to flush as much air as possible from the system.
24.  Open the air vent at the top of the collector array until 
all of the air has been dispersed then close the air vent.
25.  Open the vent on the air scoop (j) with a flat head 
screwdriver. This will release air that has been captured 
by the system during circulation. Cover small outlet 
port with a rag as fluid will be ejected after the air is 
evacuated.
26.  Turn the supply ball valve (b) to 0° (vertical) so that flow 
is only allow in the proper direction.
27.  With the transfer pump still running close the drain valve 
(h) and allow the system to rise to an operating pressure 
of 30 psi on the pressure gauge then close the fill valve 
and turn off the pump. If the pressure has exceeded 
30 psi after the pump is off the slowly open the drain 
valve (h) and relieve pressure until the pressure gauge 
reads 30 psi. then close the drain valve.
28.  Connect the expansion tank and verify the system 
pressure. If it has dropped open the fill valve (d) and 
turn on the transfer pump. Repeat system pressure 
setting in step 27.
29.  Remove the fill and drain hoses and close the fill and 
drain valves (d, h) with the caps provided. The caps 
only serve to protect the valves against dirt. They are 
not designed to withstand high system pressures, the 
valves must be closed.
Figure 28.
30.  Plug in the solar pump station to a 115V outlet and 
turn the pump on using the manual mode (see control 
operation section).
31.  Switch on the pumps using the manual mode. 
32.  Adjust the solar pump speed using the pump speed 
selector on the side of the pump (f). Set the speed to 
the lowest level possible to achieve the recommended 
system flow rate. See Table 5.
NUMBER OF COLLECTORS
1 2 3 4
COLLECTOR 
SIZE
3.5’ x 7’ 0.7 1.4 2.1 2.8
4’ x 8’ 1.0 2.0 3.0 4.0
4’ x 10’ 1.3 2.6 3.8 5.0
FLOW RATE IN GPM
Table 5.
  Adjust the storage tank pump speed using the pump 
speed selector on the side of the pump (B). Set the speed 
to be one level lower than that of the solar pump.
  Cycle the pumps on and off in manual mode to check 
whether the starting torque is sufficient with the pump 
speed selected. If flow does not start properly a higher 
speed may need to be selected. Again check the 
installation for leaks and ensure both ball valves are 
open completely.
33.  Re-insert the temperature gauges and replace the 
front cover.
34.  Set both pumps on the controller to operate in automatic 
mode. See control operation section.
35.  After the system has been running for several days 
open the air vent at the top of the collector array until 
all of the air has been dispersed then close the air vent.
DRAINING 
1.  Switch off the controller by unplugging the power supply 
from the outlet.
2.  Open the check valves in the supply and the return ball 
valves (a,b) by turning the ball valves to position 45° 
with an appropriate wrench 
3.  Place a temperature-resistant container under the drain 
valve (h)
4.  Connect a temperature resistant hose to the drain 
valve (h) with the discharge end placed in the collection 
container
5.  Open the drain valve.
6.  Open the air vent at the top of the collector array. This 
will serve as a vacuum break to aid in draining.
7.  Dispose of the solar fluid observing any local codes.
ATTENTION: Upon completion of the pump station 
installation and prior to the pump station start-up the 
included pump station valve diagram label must be attached 
to the pump station piping so that it is in plain view.










