User Manual
30
n1%, n2%:
Current pump speed
Display range 30 to 100%
Indicates the current pump speed of the corresponding pump:
-  n1%: current pump speed pump 1 – primary loop
-  n2%: current pump speed pump 2 – secondary loop
h P1, h P2
Operating hours counter
Display channel
The operating hours counter adds up the solar operating hours 
of the respective relay (h P1, h P2). Full hours are shown on 
the display.
The total operating hours can be reset. When the operating 
hours channel is selected the symbol   is permanently 
shown in the display. The set button (3) must be pressed for 
approximately 2 seconds in order to go into the reset mode 
for the counter. The display symbol    will be  ashing 
and the operating hours will be set to 0. In order to nish the 
reset procedure the set button (3) must be pressed in order to 
conrm.
In order to interrupt the reset procedure no button should be 
pressed for about 5 seconds. The controller will automatically 
return to the indication mode with the previous total.
kWh/MWh:
Heat quantity value shown 
in the kWh and MWh display 
channels. The sum of both 
channels form the total heat 
output.
The total heat quantity value can be reset. When one of the 
heat quantity display channels is selected the symbol   is 
permanently shown in the display. The set button (3) must be 
pressed for approximately 2 seconds in order to go into the 
reset mode for the counter. The display symbol   will be 
ashing and the value for heat quantity will be set to 0. In order 
to nish the reset procedure the set button (3) must be pressed 
in order to conrm.
In order to interrupt the reset procedure no button should be 
pressed for about 5 seconds. The controller will automatically 
return to the indication mode with the previous total.
TIME:
Current time based on 24 
hour clock, e.g. 15:00 = 3 pm
To set the current time:
Press button 3 for two seconds to adjust the hours
Set the hours by pressing buttons 1 and 2
Press button 3 again to set the minutes
Set the minutes by pressing buttons 1 and 2
Press button 3 in order to save the adjustments
Once the nal display channel is reached the remaining system setting channels may only be accessed by holding the 
forward (2) button down for approximately 2 seconds. The following setting channels will then be shown:
Adjustment channels:
DT1O / DT20:
Switch-on temperature diff.
Adjustment range
2.0 to 40.0 °F
Recommended setting: 10.0
The controller works as a standard differential controller. It 
calculates the temperature difference between the collector 
sensor S1 and the tank temperature sensor S3. If this 
temperature difference reaches the switch-on temperature 
difference DT1O, the primary loop pump is switched on. If 
the temperature difference falls below the switch-off difference 
DTF, the pump is switched off.
DT F:
Switch-off temperature diff.
Adjustment range
1.0 to 39.0 °F
Recommended setting: 4.0
If the switch-on temperature difference between the upper heat 
exchanger sensor S4 and the tank temperature sensor S3 is 
reached (DT2O), the secondary loop pump will be switched on.