Installation Guide

SteamSpa PHONE: 800-856-0172 FAX: 866-560-1060 http://steamspa.com info@steamspa.com
Page 14
INSTALLATION & USER GUIDE
The data provided above is for 240V single-phased motors. Install an independent circuit breaker between supply line and steam
generator. Install a power disconnect within sight of steam generator to cut-off power when not in use.
ASSEMBLY GRAPH FOR POWER WIRE
ATTENTION! To avoid damage to the equipment, do not connect electric current directly to heating elements.
WARNING! This graph is for explanation only. For actual installation, refer to national and local electricity consumption codes by
professional electricians.
Ampere Meter
Ty p e Powe r KW
S600
S750
6
7.5
9
240V
240V
240V
25
32
38
10
8
8
150
225
300
Ap pli cab l e sp ace o f
the room (cu.Ft . *)
E l e c t r i c i t y
supply (1PH)
E l e c t r i c
current (A)
Speci ficat i ons for
power wire (AWG)
10.5
240V 44 6400
12
240V
50
6
450
S900
S1050
S1200
S450
4.5 240V
19
12
90
240V
( 2 4 0 V ~ 1PH)
Power co nnectio n term inal
( 4 . 5 - 1 2kW )
L1
Ground Hot
L2
L1 L2
L2
L1