User manual

4 Installation
4.1 Safety measures during installation
Observe the following safety notes when performing the work described in Section Installation .
DANGER!
Risk of death by electrocution!
Only technical professionals may perform the work described in Section Installation .
Do not connect cables to the inverter until explicitly asked to do so in the manual.
Do not open the housing of the inverter.
Connect only SELV circuits to the RJ45 sockets.
Lay the cables such that the connection cannot come loose accidentally.
When laying cables, ensure that no damage occurs to any of the constructional fire
safety measures in the building.
Make sure that no inflammable gases are present.
Observe all applicable installation regulations and standards, national laws and connec-
tion values specified by the regional power supply company.
DANGER!
Danger from electrical current
ELECTRICAL SHOCK AND DISCHARGE!
The PV generators/lines may be energised as soon as the PV generators are exposed to light.
Always disconnect all DC and AC cables as follows before starting work on the inverter:
1. Turn the AC circuit breaker to off. Take measures to prevent the system from being uninten-
tionally switched on again.
2. Set the DC circuit breaker on the inverter to position 0. Take measures to prevent the system
from being unintentionally switched on again.
3. Disconnect the DC cable plug connectors according to the manufacturer's instructions.
4. Disconnecting the AC plug from the inverter Release safety clip at the front of the AC plug
by depressing it with a suitable object, then pull the plug out.
5. Check that all pins of the AC plug are free of voltage. Use a suitable voltmeter for this (do
not use a simple neon phase checker).
EN
747.431 | Z09.3 | 2017-09-05