User manual
NOTICE!
Risk of damage to the inverter or derating!
– The mounting location must satisfy the following conditions:
– The mounting location and immediate environment are permanently fixed, vertical,
flat, non-inflammable and not subject to constant vibration.
– The permissible ambient conditions are conformed to; see Technical data
Ä
Chapter 9 „Technical data“ on page 80
– The following free spaces must be present around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
– Do not install the inverter in areas where animals are kept.
– Observe the connection ratings specified on the type plate.
– The DC cables must not be connected to an earth potential (DC inputs and AC output
are not galvanically isolated).
NOTICE!
When transmitting data over a public network:
– Transmitting data over a public network may result in additional costs.
– Data transmitted over a public network is not protected from unauthorised access by
third-parties.
Note
– Avoid exposing the inverter to direct sunlight.
– The display must be readable on the installed device.