User manual

6 Self test
The self test is mandatory for operation of inverters in Italy.
Function
The prerequisites for performing the self test are as follows:
n The country
Italy
was selected during initial commissioning.
n The level of solar irradiation is high enough to ensure that the inverter can feed the grid.
During the self test, the inverter checks its switch-off behaviour with regard to too high / too low
grid voltage and frequency (6 test phases, duration of approx. 40 minutes). The following applies:
n In each phase of the self test, the inverter changes its switch-off threshold, step-by-step
upwards/downwards from the set lower/upper limit values.
n When the switch-off threshold reaches the actual grid voltage/frequency then the inverter
stores this information.
n The data is shown on the display as follows:
The current values of the
first
test phase are displayed first; see the following illustration.
The values of the subsequent test phases are added below (initially hidden).
If the self test succeeded then the message Self test passed is added below. The mes-
sage must be displayed and confirmed.
n If the self test conditions are not satisfied, one of the
Ä Messages of errors that prevent the
self test from running, p. 127
is displayed.
n If a measurement lies outside the required tolerance during the self test then the self test is
cancelled and the inverter displays the message Self test failed. The inverter remains dis-
connected from the grid (relay open, no feeding) until the self test is passed successfully.
Note
The data stored in the inverter can be read using a PC and the InverterSelftestProtocol software.
More information on this is provided in the StecaGrid Service_InverterSelftestProtocol manual and
at
www.stecasolar.com PV grid connected Software.
Lower / upper limit value according to the country setting
Measured actual grid voltage / frequency
Switch-off threshold (changed in steps)
Switch-off time = time between following events:
n Switch-off threshold reaches the actual grid voltage / fre-
quency
n The inverter disconnects itself from the grid
GB
747.431 | Z08 | 2014-01-31
126