User manual

StecaGrid 3000 StecaGrid 3600/x StecaGrid 4200/x
coolcept CE symbol, VDE AR N 4105, G83,
UTE C 15-712-1, AS4777, CEI 0-21
CE symbol, VDE AR
N 4105, G83, CEI
0-21
coolcept-x CE symbol, VDE AR N 4105, G83
under preparation: AS4777, CEI 0-21
Technical data at 25 °C / 77 °F
1)
The design of the inverter prevents it from causing DC leakage current.
9.2
AC cables and line circuit breakers
Conductor cross-sections of the AC cables and suitable line circuit breakers
Inverter
AC cable conductor
cross-section
Power loss
1)
Line circuit breaker
StecaGrid 1800 /-x 1,5 mm² 15 W B16
2,5 mm² 9 W B16
4,0 mm² 6 W B16
StecaGrid 2300/-x 1,5 mm² 24 W B16
2,5 mm² 14 W B16
4,0 mm² 9 W B16
StecaGrid 3000
StecaGrid 3010
/-x
2,5 mm² 25 W B16 or B25
4,0 mm² 15 W B16 or B25
StecaGrid 3600/-x 2,5 mm² 35 W B25
4,0 mm² 22 W B25
StecaGrid 4200/-x 2,5 mm² 48 W B25
4,0 mm² 30 W B25
1)
Power loss of the AC cables at the rated power of the inverter and a cable length of 10 m
GB
747.431 | Z08 | 2014-01-31