User manual
32
741.011 | 12.18
EN
11.3.7  Heat quantity
T
T
F
unc
SET
h
off
Calculates the acquired heat volume based on the following information: 
• Supply temperature
• Return temperature
• Flow rate volume determined via calculations based on the pump 
speed or by pulse water meter measurements (terminal 5).
  Note 
Calculation based on the pump speed cannot be performed when 
No System (System 0.1) has been selected.
• Glycol proportion and accounting for the temperature-dependent 
thermophysical properties of the heat transfer fluid.
Additional possibility: Display of the amount of CO
2
 saved by using the 
system. The amount of CO
2
 is calculated from the acquired heat volume. 
To do this, the controller requires the conversion factor g
CO2
/kWh
therm
 to 
be entered. 
Display Characteristic min. max.
Factory 
setting
Activation on, oFF
oFF
F
unc
SET
off
Type of flow rate acquisition tyP 1, tyP 2 
1)
–
F
unc
SET
max
Type 1: Flow rate value at max. 
pump speed F
max.
. 
When the Fig. at the left is dis-
played (value flashes) then enter 
the value read from the flow rate 
display.
F
min.
99.9 l/min 0.0 l/min
F
unc
SET
min
Type 1: Flow rate value at min. 
pump speed F
min.
. 
When the Fig. at the left is dis-
played (value flashes) then enter 
the value read from the flow rate 
display.
0.0 l/min F
max.
0.0 l/min
V
F
unc
SET
Type 2: Flow rate of the pulse 
water meter in litres/pulse; see 
the pulse water meter data 
sheet.
1L, 10L, 25L –L 
(no flow 
rate value 
selected)
Glycol proportion 0 % 60 % 40 %
Supply sensor input (warm) 1 ... 5 –
Return sensor input (cold) 1 ... 5 –
T
T
F
unc
SET
on
CO
2
 display on, oFF
oFF