11.3.13  Differential thermostat
T
T
F
unc
SET
off
Switches output R1 on and off as follows – time restricted and depend-
ing on the set temperature difference between 2 selectable sensors: 
When the temperature difference exceeds T
diff on
, the output is switched 
on until the temperature difference drops below T
diff off
. In addition to 
this, the discharging of the heating source can be limited to a particular 
temperature range (T
src min.
/T
src max.
) and the loading of the heating target 
can be limited to a maximum value(T
sink max.
).
Time restriction: The function is executed when the current time lies 
within one of 3 configurable time windows.
Speed control of the pump can be activated as required. The loading 
strategy of the speed control system attempts to regulate the tempera-
ture difference to match the switch-on temperature difference that has 
been set.
Display Characteristic min. max.
Factory 
setting
Activation on, oFF
oFF
Pump type AC, HE 
1) 2)
AC
Pump characteristics (only HE) AA, Ab, C (see p. 15)
–
Speed control on, oFF 
2)
oFF
Minimum speed (only AC) 30 % 100 % 50 %
Minimum speed (only HE + AA) 0 % 100 % 25 %
Minimum speed (only HE + Ab) 0 % 100 % 75 %
Heat source sensor input 1 ... 5 –
Heat sink sensor input 1 ... 5 –
Switch-on temperature difference 
T
diff on
T
diff off
 + 2 K 80 K 6 K
Switch-off temperature difference 
T
diff off
0 K T
diff on
 – 2 K 3 K
T
F
unc
SET
C
max
Heat source max. temperature 
T
src max.
T
src min.
 + 2 K 180 °C 100 °C
T
F
unc
SET
C
min
Heat source min. temperature 
T
src min.
0 °C T
src max.
 – 2 K 0 °C