The controller has detected faulty operation 
of the system. This is probably caused by 
swapped collector connections.
Check the collector con-
nections. 
A short-circuit exists at output R1, the pump 
connected to output R1 flashes. Possible 
causes: 
• The pump is faulty.
• Wiring fault
• Check the pump.
• Check the wiring to 
R1.
Output R1 is overloaded, the pump connect-
ed to output R1 flashes. Cause: The permis-
sible values for R1 specified on the type plate 
have been permanently exceeded, the output 
has been switched off.
Check the electrical data 
of the pump, replace 
pump if necessary. R1 is 
automatically switched on 
again. 
Tab. 6:  Error messages
15.3  Checking the Pt1000 temperature sensors
   Danger
Risk of death by electrocution! Before opening the device, make sure that all cables 
leading to the device have been disconnected from the mains power and cannot be 
unintentionally reconnected to the mains power. 
1.  Remove the terminal cover.
2.  Disconnect the temperature sensor.
3.  Measure the resistance of the temperature sensor with an ohmmeter and compare 
with Tab. 7. Small deviations are acceptable.
4.  Mount the terminal cover.
Temperature [°C] -30 -20 -10 0 10 20 30 40 50 60 70
Resistance[Ω] 882 922 961 1000 1039 1078 1117 1155 1194 1232 1271
Temperature [°C] 80 90 100 110 120 130 140 150 160 170 180
Resistance[Ω] 1309 1347 1385 1423 1461 1498 1536 1573 1611 1648 1685
Tab. 7:  Pt1000 – Temperature/resistance assignments