Cut Sheet

Spacers
F-82
Non-Metallic Rigid Conduit, Fittings and Accessories
Dimensions — Base Spacers
Carlon
®
Snap-Loc
®
Spacers
(continued)
CAT. NO. SIZE (IN.) A (IN.) C (IN.) D (DIA.) (IN.) STD. CTN.
S288JHN 2 x 1
1
2 4.25 4.12 2.50 100
S288JJN 2 x 2 4.25 4.62 2.50 100
S288JLN 2 x 3 4.25 5.62 2.50 100
S288LHN 3 x 1
1
2 4.81 5.25 3.63 90
S288LJN 3 x 2 4.81 5.75 3.63 80
S288LLN 3 x 3 4.81 6.75 3.63 60
S288NFN 4 x 1 4.50 5.75 4.63 70
S288NHN 4 x 1
1
2 5.31 6.25 4.63 50
S288NJN 4 x 2 5.31 6.75 4.63 50
S288NLN 4 x 3 5.31 7.75 4.63 60
S288PHN 5 x 1
1
2 5.84 7.31 5.69 50
S288PJN 5 x 2 5.84 7.81 5.69 60
S288PLN 5 x 3 5.84 8.81 5.69 50
S288RHN 6 x 1
1
2 6.38 8.38 6.75 50
S288RJN 6 x 2 6.38 8.88 6.75 50
S288RLN 6 x 3 6.38 9.88 6.75 40
S288SHN 8 x 1
1
2 7.38 10.30 8.75 30
S288SJN 8 x 2 7.38 10.76 8.75 30
Accessories
Dimensions — Intermediate Spacers
CAT. NO. SIZE (IN.) A (IN.) C (IN.) D (DIA.) (IN.) STD. CTN.
S289JHN 2 x 1
1
2 3.88 4.12 2.50 120
S289JJN 2 x 2 4.38 4.62 2.50 100
S289JLN 2 x 3 5.38 5.62 2.50 80
S289LHN 3 x 1
1
2 5.01 5.25 3.63 100
S289LJN 3 x 2 5.51 5.75 3.63 80
S289LLN 3 x 3 6.51 6.75 3.63 60
S289NFN 4 x 1 5.51 5.73 4.63 70
S289NHN 4 x 1
1
2 6.01 6.25 4.63 60
S289NJN 4 x 2 6.51 6.75 4.63 60
S289NLN 4 x 3 7.51 7.75 4.63 50
S289PHN 5 x 1
1
2 7.07 7.31 5.69 50
S289PJN 5 x 2 7.57 7.81 5.69 50
S289PLN 5 x 3 8.57 8.81 5.69 30
S289RHN 6 x 1
1
2 8.14 8.38 6.75 50
S289RJN 6 x 2 8.64 8.88 6.75 40
S289RLN 6 x 3 9.64 9.88 6.75 30
S289SHN 8 x 1
1
2 10.14 10.30 8.75 30
S289SJN 8 x 2 10.64 10.76 8.75 30
*First number indicates trade size of duct, second number indicates separation between conduits or ducts.
CAT. NO. SIZE (IN.) STD. CTN.
S287F 1 100
S287J 2 100
Snap-Loc
®
Reducer
CAT. NO. STD. CTN.
S258RH 100
Rebar Holder
CAT. NO. STD. CTN.
S28612 1 Bag of 250
Beaded Strap
15" in length
Specifications
B
C
A
3" Standard for all Base Spacers
(with the exception of the 4X1-S288NFN)
The Spacers and Rebar Holder are designed with a dovetail
tongue-and-groove feature for easy installation.
If required to permanently fix the position of a group of Spacers
and/or Rebar Holder, the following are recommended procedures:
1. Use Carlon
®
Quick-Set Cement glue during assembly or spot glue
after assembly to secure.
2. During assembly, deform the edge of the tongue or groove portion
of the dovetail slide with a pair of pliers or similar tool. This deformation
will create an interference, restricting movement.
3. An assembled system may be wired together for additional support.
Installation Note
Important:
The use of duct spacers for direct burial may result in excessive
point deflections unless proper design engineering is applied, such
as the proper compaction of the appropriate backfill material.
Suggested Specification:
(Duct) (Conduit) bank shall be encased in concrete with at least three inches
of concrete at the top and bottom and two inches on each side. A horizontal
and vertical separation between the ducts of ____* inches shall be
maintained by installing Carlon
®
high-impact spacers with horizontal
and vertical locking intervals of ____** feet.
*Standard Separations of 1", 1
1
2", 2" and 3" are available.
**Preferred interval between spacer assemblies is 8 to 10 feet.
Hole Dia. = .688 min.
.750 max.