Datasheet
50
PRODUCT CATALOGUE - STEGOCOOLING
FILTER FAN PLUS
FPI/FPO 018 |
up to 263 m³/h (176 x 176 mm)
TECHNICAL DATA
Axial fan, ball bearing service life L10 at +40 °C (+104 °F): min. 65,000 h
fan body aluminium, rotor metal
Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 176 x 176
+1
mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1 — 4 mm).
Additional use of screws possible if needed
1
.
Filter mat G3 acc. to DIN EN 779, average arrestance A
a
84 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100 °C, self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating temperature 50 Hz: -25 to +50 °C (-13 to +122 °F)
60 Hz: -25 to +70 °C (-13 to +158 °F)
Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request
AIRFLOW DIRECTION "IN": FILTER FAN FPI 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01872.0-30 AC 230 V, 50/60 Hz 170 m³/h 139 m³/h 310/250 mA 45 W 55 db (A) 117 mm 1.6 kg G3
01872.9-30 AC 115 V, 50/60 Hz 204 m³/h 187 m³/h 560/470 mA 38 W 58 db (A) 117 mm 1.6 kg G3
AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118
Art. No. Depth in enclosure Weight (approx.) Air outlet
11872.0-00 43 mm 0.4 kg air-flap outlet technology
1
Drilling marks for screw mounting are indicated on mounting frame.
Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components.
The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure
thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations
and protects electronic components from overheating.
The Filter Fan Plus series uses a new air-flap outlet technology for the air outlet and thus reaches a high degree
of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the
application there are two systems that are available – the FPI or FPO system. The FPI system is a standard installation
with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow
direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located
in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of
an intake filter and exit filter fan. The Filter Fan Plus series has been designed for indoor use.
> New air-flap outlet technology for
high airflow
> Easy mounting
> Protection type test/Environmental
rating by independent testing institutes
(VDE and UL)
> Two systems for optimal airflow
(FPI/FPO)
> Standard enclosure cut-out sizes
(5 sizes)
> One filter mat
warmcold
Exit Filter FPI 118
Filter Fan FPI 018
Air-flaps
Filter mat
SYSTEM FPI
30.11.2017 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
50
TECHNICAL DATASHEET