Datasheet

1
warmcold
Exhaust Filter FPI 118
Filter Fan FPI 018
Air-flaps
Filter mat
SYSTEM FPI
TECHNICAL DATA
Axial fan, ball bearing service life L10 at +104 °F (+40 °C): min. 76,000 h
metal impeller
Connection 3-pole clamp for AWG 14 (2.5 mm²), clamping torque 0.8 Nm max.
Housing, hood, fl aps plastic UL 94V-0, light grey;
UV light resistant according to UL 746C (f1)
Enclosure cut-out
11.46 x 11.46
+0.04
inches (291 x 291
+1
mm)
Mounting frame 4 built-in ratchet push levers for mounting (6 ratchet stops to
accommodate for wall thicknesses Gauge 9 to 19 or 1-4 mm).
Additional screw mounting possible if needed
1
.
Filter mat G3 acc. to DIN EN 779, average arrestance A
a
84 %
Filter material synthetic mesh with progressive construction,
temperature resistant to +212 °F (+100 °C), self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating temperature 50 Hz: -13 to +131 °F (-25 to +55 °C)
60 Hz: -13 to +95 °F (-25 to +35 °C)
Storage temperature -40 to +158 °F (-40 to +70 °C)
Operating/Storage humidity max. 75 % RH (non-condensing)
Protection type/Protection class IP54 / I (grounded)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request
Filter fans are used to provide "cooling" by forced air-circulation in enclosures and cabinets containing eletrical/
electronic and other components. The interior temperature of an enclosure can be reduced by channelling cooler,
ltered outside air into the enclosure, thus expelling hot inside air. The resulting airfl ow prevents formation of
localized hot pockets and protects electronic components from overheating.
The Filter Fan Plus series encompasses a new air-fl ap technology on the air outlet side, thereby reaching an
unparalleled high degree of airfl ow. A unique ratchet mechanism is used for easy installation. It provides safe and
secure mounting while guaranteeing a tight seal. Depending on the requirements, there are two optional systems
available – the FPI or the FPO system (FPI = "in", FPO = "out"). The FPI system is the more commonly known
installation system, where a fi lter fan located in the lower part of the enclosure draws cleaner, cooler air into the
enclosure (airfl ow direction "In"). This system consists of a fi lter fan and exhaust fi lter. On opposite, with the newer
FPO system, the fi lter fan will be located in the upper area of the enclosure to draw warmer air out of the enclosure
(airfl ow direction "Out"). The FPO system consists of an intake fi lter and exhaust fi lter fan. The Filter Fan Plus series
has been designed for indoor use.
FILTER FAN PLUS
FPI/FPO |
11.46 X 11.46" (291 X 291 MM)
AIRFLOW DIRECTION "IN": FILTER FAN FPI 018
Part No. Operating voltage Air volume,
free blowing
Air volume
with exhaust fi lter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Mounting depth Weight
(approx.)
Filter mat
01874.0-30 AC 230 V, 50/60 Hz 254.8 cfm (433m³/h) 219.5 cfm (373 m³/h) 400/480 mA 95 W 62 dB (A) 6.3" (160 mm) 6.8 lbs. (3.1 kg) G3
01874.9-30 AC 115 V, 50/60 Hz 231.9 cfm (394 m³/h) 199.5 cfm (339 m³/h) 660/800 mA 90 W 61 dB (A) 6.3" (160 mm) 6.8 lbs. (3.1 kg) G3
AIRFLOW DIRECTION "IN": EXHAUST FILTER FPI 118
Part No. Mounting depth Weight (approx.) Air outlet
11874.0-00 2.0" (50 mm) 2.2 lbs. (1.0 kg) air-fl ap outlet technology
1
Drilling hole markings for screw mounting are indicated on mounting frame.
> New air-fl ap outlet technology for
high airfl ow
> Easy mounting
> Protection type/Environmental
ratings by independent testing
agencies (VDE & UL)
> Two optional systems for optimal
airfl ow (FPI/FPO)
> Industry-common enclosure cut-out
sizes (5 sizes)
> Single fi lter mat system design
29.11.2016 | Speci cations are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its nal application. www.stegousa.com
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com

Summary of content (2 pages)