Datasheet

36
PRODUCT CATALOGUE - STEGOCOOLING
Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components.
The interior temperature of an enclosure can be reduced by channelling cooler fi ltered outside air into the enclosure
thus expelling heated internal air. The resulting airfl ow prevents formation of localised hot pockets in installations
and protects electronic components from overheating.
The Filter Fan Plus series uses a new air- ap outlet technology for the air outlet and thus reaches a high degree
of airfl ow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the
application there are two systems that are available – the FPI or FPO system. The FPI system is a standard installation
with a fi lter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airfl ow
direction "In"). This system consists of a fi lter fan and exit fi lter. Whereas in the FPO system, the fi lter fan is located
in the upper area of the enclosure to avoid heat buildups (airfl ow direction "Out"). The FPO system is composed of
an intake fi lter and exit fi lter fan. The Filter Fan Plus series has been designed for indoor use.
FILTER FAN PLUS
FPI/FPO 018 |
up to 24m³/h (92 x 92mm)
TECHNICAL DATA
Axial fan, ball bearing service life L10 at +40°C (+104°F): min. 50,000h
fan body aluminium, rotor metal
Connection 2 stranded wires, 300mm
Casing, hood, fl aps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 92 x 92
+1
mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1 4mm).
Additional use of screws possible if needed
1
.
Filter mat G3 acc. to DIN EN 779, average arrestance A
a
84%
Filter material synthetic fi bre with progressive construction,
temperature resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating/Storage temperature -40 to +70°C (-40 to +158°F)
Operating/Storage humidity max. 90% RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request
AIRFLOW DIRECTION "IN": FILTER FAN FPI 018
Art. No. Operating voltage Air volume,
free fl ow
Air volume
with exit fi lter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01870.0-30 AC 230V, 50/60Hz 19m³/h 13m³/h 70mA 12W 39dB 66mm 0.6kg G3
01870.9-30 AC 115V, 50/60Hz 23m³/h 16m³/h 115mA 11W 43dB 66mm 0.6kg G3
AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118
Art. No. Depth in enclosure Weight (approx.) Air outlet
11870.0-00 29mm 0.2kg air-fl ap outlet technology
1
Drilling marks for screw mounting are indicated on mounting frame.
> New air-fl ap outlet technology for
high airfl ow
> Easy mounting
> Protection type test/Environmental
rating by independent testing institutes
(VDE and UL)
> Two systems for optimal airfl ow
(FPI/FPO)
> Standard enclosure cut-out sizes
(5 sizes)
> One fi lter mat
warmcold
Exit Filter FPI 118
Filter Fan FPI 018
Air-flaps
Filter mat
SYSTEM FPI
28.04.2016 | Specifi cations are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its fi nal application.
www.stego.de | www.stego.co.uk | www.stegonorden.se
36
TECHNICAL DATASHEET

Summary of content (2 pages)