User manual

– 18 – – 19 –
Troubleshooting
Malfunction Cause Remedy
IS 180-2
without power
Fuse faulty; not switched
ON
Short circuit
Mains switch OFF
Renew fuse, switch on
mains power switch,
check wiring with voltage
tester
Check connections
Switch on
IS 180-2 will not switch
ON
Twilight control set to
nighttime mode during
daytime operation
Bulb faulty
Mains power switch OFF
Fuse faulty
Detection zone not
properly targeted
Adjust setting
Change light bulb
Switch on
Renew fuse, check
connection if necessary
Re-adjust
IS 180-2 will not switch
OFF
Continuous movement in
the detection zone
Light is in detection zone
and keeps switching on
as a result of tempera-
ture change
Set to continuous
operation by indoor
series switch
Check detection zone
and re-adjust if
necessary or fi t shrouds
Re-adjust zone or apply
shroud
Set series switch to
automatic mode
IS 180-2 keeps switching
ON/OFF
Light is in detection zone
Animals moving in
detection zone
Heat source (e.g.
extractor hood outlet) in
detection zone
Adjust detection zone
or fi t shrouds, increase
distance
Adjust detection zone or
t shrouds
Adjust detection zone or
t shrouds
IS 180-2 switches on when
it should not
Wind is moving trees and
bushes in the detection
zone
Cars in the street are
being detected
Sudden temperature
changes due to weather
(wind, rain, snow) or air
expelled from fans or
open windows
Blank off sections using
shrouds
Blank off sections using
shrouds
Adjust detection zone or
change site of installation
Operation/Maintenance
The Infrared Sensor is
suitable for switching light
on and off automatically.
The unit is not suitable for
special burglary alarm
systems since it lacks
the tampering protection
prescribed for this purpose.
Weather conditions may
affect the way the motion
detector works. Strong
gusts of wind, snow, rain
or hail may cause the light
to come on when it is not
wanted because the sensor
is unable to distinguish
sudden changes of tem-
perature from sources of
heat. The detector lens may
be cleaned with a damp
cloth if it gets dirty (do not
use cleaning agents).
Wiring examples
1. Light without neutral conductor 2. Light with neutral conductor
3. Connection using series switch for
manual and automatic operation
4. Connection to double-throw switch
for permanent light ON and automatic
operation
Setting I: automatic operation
Setting II: manual operation for permanent
light ON
Important: the unit cannot be switched
OFF, but operated only at settings I and II.
1) e.g. 1-4 x 100 W fi lament bulbs
2) Service load, light of 1000 W max. (see Technical specifi cations)
3) IS 180-2 connection terminals
4) Indoor switch
5) Indoor series switch, manual, automatic
6) Indoor double-throw switch, automatic, permanent light ON
GB