Instructions / Assembly

INSASIRH0117
5
= 25 à 60°
minimum
24"
[610 mm]
minimum
20"
[510 mm]
minimum
30"
[760 mm]
VUE DE CÔTÉ
minimum
30"
[760 mm]
minimum
20"
[510 mm]
minimum
30"
[760 mm]
20"
[510 mm]
VUE DE CÔTÉVUE DE FACE VUE DE CÔTÉ
INSTALLATION MURALE INSTALLATION AU PLAFOND
H
H
= 25 à 60°
minimum
21"
[533 mm]
minimum
20"
[510 mm]
minimum
26"
[660 mm]
VUE DE CÔTÉ
minimum
26"
[660 mm]
minimum
20"
[510 mm]
minimum
26"
[660 mm]
12"
[305 mm]
VUE DE CÔTÉVUE DE FACE
INSTALLATION MURALE INSTALLATION AU PLAFOND
VUE DE CÔTÉ
H
H
4000 W / 3200 W AT 240 V / 208 V & 4200 W AT 347 V UNITS
6000 W / 4800 W AT 240 V / 208 V UNITS
It is very important to respect the clearance from ammable material, as mentioned below.
It is very important to respect the clearance from ammable material, as mentioned below.
All ammable
items must be
at least 48”
(1.22 m) from
the front of the
unit.
All ammable
items must be
at least 60”
(1.525 m) from
the front of the
unit.
WALL INSTALLATION
WALL INSTALLATION
CEILING INSTALLATION
CEILING INSTALLATION
SIDE
SIDE
SIDE
SIDE
SIDE
SIDE
FRONT
FRONT
Connect the power leads in accordance with the electrical codes in effect. Make sure the line voltage (volt) is consistent with that indicated on
the unit’s nameplate.
Each unit is equipped with power leads that come in a exible metallic duct and with a connector that is ready to be connected to an electrical
box (not included).
N.B. This product must be connected by a qualied electrician according to the electrical and building codes effective in your region.
ELECTRICAL CONNECTIONS
L1
LAMPE 1
LAMPE 2
L2
LAMPE 3
GN
D
L1
L2
LAMPE 1
LAMPE 2
LAMPE 3 L2
PARALLEL CONNECTION OF THE LAMPS:
ASIRH1501W, ASIRH2002W, ASIRH4002W
AND ASIRH6002W MODELS
SERIES CONNECTION OF THE LAMPS:
ASIRH4203W MODEL
LAMP 1 LAMP 1
LAMP 2
LAMP 2
LAMP 3
LAMP 3
INSTALLATION