User's Manual

Aeris Installation, Service and Troubleshooting Manual
Page | 42
Regulator Setting
It’s recommended that you check the regulator pressure 4 times a year to verify the
regulator is still set at the desired pressure setting.
Open the cover to the control box.
Remove the metal cap on the check port fitting on the regulator.
Check the pressure with an accurate gauge, such as a master gauge.
If the pressure is correct, replace metal cap and close the lid.
If the pressure is above or below the desired setting, adjust the pressure using the
adjustment knob. See Figure 36.
If the pressure is “low” pull up on the regulator’s knob to unlock. Turn the knob
clockwise to increase the pressure. Allow the pressure to stabilize then check the
pressure 2-3 times to verify correct pressure. If the pressure is correct, push the
knob back down to lock in place and replace the metal cap.
If the pressure is “high” turn the knob counter-clockwise to decrease the pressure.
Allow the system to stabilize and check the pressure 2-3 times to verify correct
pressure. Continue to decrease or increase the regulator until the desired pressure
is achieved.
Figure 36