VENTING – GENERAL GUIDELINES
Vent Systems Termination Clearance Requirements
Structure/Object
Minimum Clearance for Termination Locations
USA CANADA
Door, window, or gravity vent inlet;
combustion air inlet for other appliances
9 in. for 10,000 to 50,000 BTU/Hr input; 12 in. for input
exceeding 50,000 BTU/Hr.
9 in. (230mm) for 10,000 to 50,000 BTU/Hr input; 12 in.
(305mm) for input exceeding 50,000 BTU/Hr.
Forced air inlet within 10 ft.
3 ft. above 6 ft. (1.8m)
Adjoining Building or parapet 10 ft. 10 ft. (3.04m)
Adjacent public walkways
7 ft. above
grade
7 ft. (2.1m) above grade
Electric, gas meters & regulators 4 ft. horizontal
3 ft. (0.9m) horizontally from meter/regulator assembly. 6 ft.
(1.8m), any direction, from a gas service regulator vent outlet
Above grade level* 1 ft. 1 ft. (0.3m)
*Minimum above maximum snow depth, or per local code, whichever is greater.
Table 5
Figure 8 – Size 50 Filter Box Assembly Installation
FILTER
GASKET
FILTER BOX
CAT-10295A
The lter box must be installed prior to unit operation. Failure to do so may result in damage
to the burner assembly.
NOTICE: The lter is only designed to prevent large debris from entering the burner assembly. If there are
other contaminants in the space air, the unit should be installed as separated combustion to take outside
air into the unit for combustion.