RSD Series Submittal

3
2
)
MINIMUM CLEARANCES TO COMBUSTIBLES
Minimum clearances shall be measured from the outer surfaces as shown below:
MINIMUM CLEARANCES TO COMBUSTIBLES
Mounted Horizontally Mounted at 35° Angle
Below Below Front
w/Standard
Refl ector
w/Refl ector
Extension
w/Standard
Refl ector
w/Refl ector
Extension
w/Standard
Refl ector
w/Refl ector
Extension
Angle
Model Sides Ceiling Rear Mounting
RSD30 RSD35 0° min
RSD33 RSD40 30" 36" 72" 100" 72" 100" 36" 50" 30" 35° max
RSD60 RSD70 0° min
RSD66 RSD80 48" 48" 98" 137" 98" 137" 48" 68" 36" 35° max
RSD100 0° min
RSD120 48" 64" 128" 180" 128" 180" 60" 84" 48" 35° max
RSD132 RSD160 10° min
RSD140 60" 64" 136" 190" 136" 190" 64" 90" 48" 35° max
NOTE: The clearances specifi ed above must be maintained to combustibles and other materials that may be damaged by
temperatures 90°F above ambient temperature. It is the installer’s responsibility to ensure that building materials with a low heat
tolerance which may degrade at lower temperatures are protected to prevent degradation. Clearances to combustibles are posted
on the refl ector near the control end of the heater. In locations used for storage of combustible materials where they may be stacked
below the heater, NFPA 54 requires that the installer must post signs that will “specify the maximum permissible stacking height to
maintain the required clearances from the heater to combustibles. Manufacturer recommends posting these signs adjacent to the
heater thermostat or other suitable location that will provide enhanced visibility.
STERLING “RSD” SERIES
INFRARED RADIANT HEATER