RSG Heater Series Submittal

11
C. LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS – SINGLE HEATER PER THERMOSTAT
Order 24V Relay Kit (Part No. 43274020) for Low Voltage (24V) thermostat connection.
D. LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS – MULTIPLE HEATERS PER THERMOSTAT
NOTES:
a. If any of the original wire as supplied with the appliance must be replaced, it must be replaced with
wiring material having a temperature rating of at least 105°C. (18 Ga. CSA 600V Type TEW)
b. When connecting the supply circuit to the heater, wiring material having a minimum size of 14 AWG
and a temperature rating of at least 90°C shall be used.
c. A replaceable 2-amp fuse (1-1/4" long) is located inside the control box.
STERLING “RSG” SERIES
INFRARED RADIANT TUBE HEATER