- 7 -
Specications
Powersource 9VDCbattery(included)
Standbycurrent 45µA
Alarmcurrent 28mA(lowvolume)/32mA(highvolume)
Operatingtemperature 32°to120°F(0°to49°C)
Sounderoutput(at1m) 95–102dB
Soundertones 7
Network >2unitsspacedlessthan50mapart
Fault Finding
Asimpletestcompletedoneachindividualunitwillimmediatelyhighlightifanyofthefollowingfaultsare
evident: Low Battery condition, Network connection loss
Usingthemasterkey,turntheunit“OFF”andthenback“ON.”
Ifnoaudiblebeepssoundwithin5seconds,theunithasnofaults.
Ifashortsinglebeepsoundswithin5secondstheunithasalowbatteryfault.
Replacethebattery.
If2shortbeepssoundwithin5secondstheunithasanetworkfault.Checkallthenetworkcable
terminationsand/orthewiringassociatedwiththeinputsignaltothedevice.
Warranty
SafetyTechnologyInternational,Inc.warrantstotheoriginalconsumer/purchaserwhatthisproductshall
befreeofdefectsinmaterialandworkmanshipundernormaluseandcircumstancesforaperiodofone
(1)yearfromtheoriginaldateofpurchase.
Electronicwarrantyformatwww.sti-usa.com/wc14.
NETWORK IN
NETWORK COMMON
NETWORK OUT
EXTERNAL SOUNDER
EXTERNAL SOUNDER
+
-
Note:
All external sounders
must be hard-wired
using 2-core cable, and
must have their own
power supply.
It is recommended
that external wiring
does not exceed 50
metres.
VOLUME JUMPER CONNECTION (3 PINS)
DIP SWITCHES
PCB Terminal Diagram