OPERATING AND INSTALLATION INSTRUCTIONS SINGLE AND DUAL HEAT EXCHANGER DOMESTIC HOT WATER TANKS FOR SOLAR, GEOTHERMAL OR HYDRONIC APPLICATIONS ›› SBB 300, 400 S & SBB 300, 400, 600 PLUS SBB tanks are ETL certified in US & Canada to IAS U.S. Requirements for Indirect Fired Water Heaters For Use With External Heat Source. No 1-91, Dated June 6, 1992. Tested and certified by WQA to NSF/ANSI 372 for lead free compliance. WWW.STIEBEL-ELTRON-USA.
1. CONTENTS SECTION 1. 2. 3. 3.1 4. 4.1 4.2 4.3 5. 6. 6.1 6.2 7. 7.1 7.1.1 7.1.2 7.2 7.3 7.4 8. 8.1 8.2 8.3 8.4 8.4.1 8.4.2 8.4.3 8.4.4 8.4.5 8.4.6 8.5 8.6 8.7 8.8 9. 10.
ENGLISH 2. SAFETY INSTRUCTIONS General Information Safety Instructions Read this entire manual. Failure to follow all the guides, instructions and rules could cause personal injury or property damage. Improper installation, adjustment, alteration, service and use of this unit can result in serious injury. WARNING: Never install any valves or shutoff devices in the piping between the collectors and the safety valve. The safety valve is actuated at 87 psi pressure.
3. OPERATION AND SERVICE 3.1 Start-up The hydronic back-up boiler (see Figure 5) and solar storage tank (see Figures 4 & 5), constitute a functional unit. Hot water is generated throughout the year by the solar collectors (see Figure 4). Supplemental heat is provided by the back-up boiler when there is insufficient solar energy available (see Figure 5). The entire heater and hot water system must be filled with water and have adaquate air ventilation.
ENGLISH 5. FAILURES – CAUSES – CORRECTION Failures Causes Correction Inadequate water pressure Shut-off valve is not completely open. Cold or hot water line is obstructed. Boiler temperature is set too low. Recommended 176 to 185 °F / 80 to 85 °C. Heat exchanger is calcified. Program selection at the heater control is not properly selected. Aerator at the extraction point blocked. Flow rate too high. Recommended 2.6-3.9 gal./min. or 9.8-14.8 l/min. Open Shut-off valve. Clean or exchange pipes.
.1 Technical Data and Specifications Model Item No. SBB 300 S 221219 SBB 400 S 221222 Contents Storage capacity Volume of heat exchanger, top Volume of heat exchanger, bottom 80.6 gal (305 l) N/A 2.7 gal (10.1 l) 108.6 gal (411 l) N/A 2.9 gal (11.3 l) Pressure Working pressure Tested to pressure Max. pressure of boiler loop 150 psi (10 bar) 217 psi (15 bar) 150 psi (10 bar) 150 psi (10 bar) 217 psi (15 bar) 150 psi (10 bar) Temperature Max. temperature lower loop Max.
Dimensions Type A B C D E F G H I J K L M N O P Height of unit w/insulation Height of unit without insulation Height of well for temp. sensor Height thermometer Height spare port Height of well for temp. sensor Height inspection flange Height cold water feed Height solar cold feed Height solar hot return Height heater hot boiler return Height circulation port Height cold boiler feed Overall height Width without thermal insulation Width with thermal insulation WWW.STIEBEL-ELTRON-USA.
7. INSTALLATION INSTRUCTIONS FOR THE PROFESSIONAL 7.1 General Figure 1 is referenced for explanation of the following text. 7.1.1 Brief Description of the Appliance - Applications The Stiebel Eltron Vertical Solar Storage tank SBB S / Plus, in combination with Stiebel Eltron’s Solar Collector is an economical hot water generator. The Stiebel Eltron Vertical Solar Storage tank SBB S / Plus, in combination with any hydronic boiler also functions as an efficient indirectly fired water heater. 7.
8.1 Set-up ENGLISH 8. SET-UP AND INSTALLATION 8.4.3 Cold Water Supply Safety Components NOTICE: THE UNIT SHOULD BE LOCATED IN AN AREA WHERE WATER LEAKAGE FROM THE UNIT OR ANY CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE AREA SURROUNDING THE UNIT. DANGER: THE UNIT MUST NOT BE LOCATED NEAR FLAMMABLE LIQUID SUCH AS GASOLINE, ADHESIVES, SOLVENTS, PAINT THINNERS, BUTANE, LIQUIFIED PROPANE, ETC. AS THE CONTROLS OF THIS APPLIANCE COULD IGNITE VAPORS CAUSING AN EXPLOSION.
| SBB S & SBB PLUS SOLAR STORAGE TANKS SS MV Check Valve Disconnect Valve Pressure Rel.
WWW.STIEBEL-ELTRON-USA.COM SS MV P T S T check valve active Check Valve Disconnect Valve Pressure Rel.
8.5 Hot water temperature probe 8.8 Sacrificial anode (spare part) The hot water temperature probe is to be installed into the upper immersions sleeve (Pos. 3, Figure 1). If a sacrificial anode is installed into the SBB S or SBB Plus storage tank, the following must be observed: Installation – sacrificial anode • Pull out the red shut-off plug while simultaneously depressing the pressure ring, (see Figure 7). • Push in the open pipe end of the indicator element until deadstop.
ENGLISH 9. TEMPERATURE & PRESSURE RELIEF VALVE ASSEMBLY 8 T&P Relief Valve Automatic-Resetting Temperature and Pressure Relief Valve 150 psi 210 °F Watts #100XL-8 3/4” NPT SE# S28640 3/4” NPTF SE# S34292 3/4” copper to Domestic Hot Water (DHW) 3/4” copper 2” of 3/4” copper SE# S258185 Figure 8: Exploded view of T&P relief valve assembly including part numbers WWW.STIEBEL-ELTRON-USA.
9 Mounted to top of SBB tank T&P Relief Valve Automatic-Resetting Temperature and Pressure Relief Valve 150 psi 210 °F Watts #100XL-8 3/4˝ NPT SE# S28640 Pressure relief safety vent pipe (3/4˝ NPTF) SE# S34292 3/4˝ copper to Domestic Hot Water (DHW) 2˝ of 3/4˝ copper SE# S258185 Complete assembly on SBB tank. Figure 9: Assembled view of T&P relief valve assembly including part numbers 14 | SBB S & SBB PLUS SOLAR STORAGE TANKS WWW.STIEBEL-ELTRON-USA.
DHW SOL AR & INDIRECT STOR AGE TANKS All SB 150 S, SB 200 S, SB 300 E, SB 400 E, SBB 300 S, SBB 400 S, SBB 300 Plus, SBB 400 Plus, & SBB 600 Plus Model s LIMITED WARRANT Y Subject to the terms and conditions set forth in this limited lifetime warranty, Stiebel Eltron, Inc. (the “Manufacturer”) hereby warrants to the original purchaser (the “Owner”) that each storage tank (the “Tank”) shall be free from defects in the Manufacturer’s materials or workmanship for a period of: 1.
STIEBEL ELTRON, Inc. 17 West Street | West Hatfield MA 01088 Tel. 413-247-3380 | Fax 413-247-3369 info@stiebel-eltron-usa.com www.stiebel-eltron-usa.