Document MN5002 ™ StorageTek D173/9176 Disk Subsystem Site Preparation Guide
™ StorageTek D173/9176 Disk Subsystem Site Preparation Guide
Information contained in this publication is subject to change. In the event of changes, the publication will be revised. Comments concerning its contents should be directed to: Disk LPO Information Developer Storage Technology Corporation One StorageTek Drive Louisville, CO 80028-2129 USA Information Control This publication and the information contained herein is the property of StorageTek.
List of Pages Document Title: StorageTek D173/9176 Disk Subsystem Site Preparation Guide Manual Part Number: MN5002F First Edition: February 2000 Second Edition: April 2000 Third Edition: August 2000 Fourth Edition: December 2000 Fifth Edition: June 2001 Sixth Edition: November 2001 Total number of pages in this document is 70, consisting of: Pages Cover Blank page Title page Copyright page iii through xii 1 through 46 Index-1 through Index-4 Reader’s Comment Form Business Reply Mailer Blank
Summary of Changes The following is the history and summary of changes for this publication. Date Edition Description February 2000 A Initial Release April 2000 B Added order information, cabinet information, modified sizes and weights, added color photographs of the 9176 and 9170, and feature codes. August 2000 C Changed solution name to StorageTek 9176 SAN Disk Array, and added more detail to various sections.
Contents Contents About the Site Preparation Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Order Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents Host Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Single-Bus Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Dual-Bus Configurations (recommended) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Other Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figures Figures 9176 Disk Subsystem - Order Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 9176 Controller Tray Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Drive Tray Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 D173 PDU for distributing Power to Devices throughout the Cabinet . . . . . . . . . . . . . . . .
Tables Tables D173 “entry level” Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 9176 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 AC Power Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 DC Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface This Site Preparation Guide is part of a four-book documentation set that supports installation, operation, troubleshooting, and servicing of the StorageTek 9176 and D173 Disk Subsystem. The Site Preparation Guide provides order information and some instructions for preparing your installation site. To plan for an installation, refer to the Planning Guide, part number MO9113Ae.
configure and manage the subsystem is called: StorageTek Object Manager. It has various software components (for example: Client, Agent, RDAC, NVSRAM, and OMutil for the management station) that enable communications between hosts, controllers, drives, and the other network devices. All these components must work together for well-orchestrated data management and performance. StorageTek and its suppliers have worked hard to validate and certify their 9176 and D173 storage subsystem configurations.
Product Compliance The StorageTek 9176 Disk Subsystem as well as all other product solutions undergo many regulatory agency tests. These tests help certify that our products meet various county and agency requirements. Product Compliance maintains a web site at: http://pct.stortek.com which defines the national, international, and corporate safety and environmental standards as well as the product compliance status for various product.
xii
About the Site Preparation Guide This document provides information about ordering and site requirements for installation of the StorageTek™ 9176 and D173 Disk Subsystems. Introduction The 9176 and D173 come in a 19 inch rackmount cabinet, already configured for the host(s). The 9176 always has at least one 9176 controller tray and one 9170 drive tray.
.............................................................................. Use this Site Preparation Guide to assist with your order (as well as the Planning Guide), and to make sure that your installation site meets all applicable environmental, power, and site requirements.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Order Information Order Information When ordering via the Siebel configurator or manually, you will need to make a decision on: • what kind of rackmount cabinet you want • the amount of storage needed • the type of channel cable to use • the amount of hosts you want to attach to your storage.
.............................................................................. The following illustration depicts this particular example 9176 Disk Subsystem configuration.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Order Information NOTE RDAC works on Windows NT, 2000, and on Solaris platforms. Other servers/ operating systems have a similar host-specific software application. In the event of a loss of a hardware device or cable-path along the way, alternate paths may be used.
.............................................................................. Table 2 Model 9176 Models Description Storage Capacity 9176-001 A 9176 Disk Controller with 256 Mbytes of cache, 2 host interface cards, and 2 drive interface cards. One 9176 subsystem can handle up to 100 drives (or use 2 Disk Controllers with nine 9170s (90 drive modules)). Forty 180 GB drives maximum. 9176-002 A 9176 Disk Controller with 512 Mbytes of cache, 4 host interface cards, and 4 drive interface cards.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.............................................................................. Installation Support If you’re planning an install, you will need to contact your StorageTek account team, who will help you configure the right solution for your business environment. They will also identify the StorageTek personnel who have been trained to install a StorageTek 9176 or D173 Disk Subsystem for a specific operating system or your entire heterogeneous storage environment.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Order Information NOTE You should also click the Other Resources button, and then go to the CRC (Customer Resource Center) where you can select the Disk Storage hyperlink. Information for both customers and employees is available here. Site Preparation Form The following should be used to plan your StorageTek 9176 Disk Subsystem installation.
.............................................................................. 2 Channel Site -- http://www.storagetek.com/channels/index.html where you select login here and then enter your username and password, and select Products >> 9176 (Client Server Disk Subsystem menu) >> Technical Info >> 9176/9170 Connectivity Information. 3 KnowledgeMap -- http://wwfokm.stortek.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Order Information Cabinet Description StorageTek provides a 19 inch rackmount cabinet for the Disk Storage environment. The cabinet conform to the EIA-310-D standard using the modular unit U to indicate panel height. The unit U equals 44.45mm or 1.75 inches. The CBNT M03 is a fixed 39U size. It allow you to easily add more storage in the future.
.............................................................................. Deskside Power The following lists the feature code and part number for the deskside (low-profile) cabinet’s power cord, available with the D173 Disk Subsystem only.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weight and Dimensions Weight and Dimensions StorageTek™ 9176 Disk Controller Tray Weight Make sure that the floor space at the installation site has sufficient stability to support the maximum weight of the controller tray and associated equipment. The controller tray’s total weight depends on the number of canisters in the tray.
.............................................................................. StorageTek™ 9176 Disk Controller Dimensions Make sure that the installation site provides at least 610 mm (2 feet) of space around the cabinet to ensure adequate ventilation (and equipment cooling). Figure 2 shows the dimensions for the deskside and rackmount controller tray and the front cover. Controller Tray Shipping Carton Dimensions — Rackmount or Deskside Unit (Includes shipping pallet) Height: 430.6 cm (16.95 in.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weight and Dimensions StorageTek™ 9170 Disk Array and D173 Disk Controller Array Weight Ensure that the site’s floor can support the total weight of all drive trays and associated equipment. The 9170/D173’s weight depends on the number of drive modules installed in the tray.
.............................................................................. 9170 Disk Array and D173 Disk Controller Array Dimensions Again, make sure that there is adequate space available in the front and back of the cabinet to enable CSEs to service the drive trays. This space is also needed to ensure proper ventilation and cooling of the StorageTek 9176/D173 Disk Subsystem. Figure 3 shows the dimensions of the rackmount and deskside drive tray.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring and Power Wiring and Power The StorageTek 9176/D173 Disk Subsystem typically comes in its own rackmount cabinet with all internal power is supplied via the cabinet’s power distribution unit (PDU). StorageTek provides a rackmount cabinet user’s guides specific to the customer’s needs.
.............................................................................. AC Power Requirements - 9176 Disk Controller Assuming a 70% power supply efficiency and a 0.99 Power Factor, the following specifications apply to a fully configured 9176 Disk Controller. Table 8 Parameter Additional Power Ratings/Specifications 110 volt 220 volt Min. Operating Current 2.0 A 1.0 A Max. Operating Current 2.0 A 1.0 A Max. Surge Current 3.0 A 2.0 A Max. Operating Power NOTE .1925 KVA, 192.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring and Power or more drive trays - using four, 90–136 volt, 15 Amp circuits. Connect half • four of the 9170 drive trays to two circuits and the remaining drive trays to the other two circuits. Make sure that each drive tray connects to two different circuits (one per power supply). AC Power, nominal 240 volt - Use two 200–264 volt, 15 Amp circuits.
.............................................................................. 9176/D173 Disk Subsystem Current Calculations With the 9176 Disk Controller (at 220v) pulling one ampere and the 9170 or D173 each pulling 1.8 amperes, a rackmount cabinet with one controller and ten disk arrays would draw a total of 19 amperes. These amps are supplied by two grids of the power distribution unit (PDU), with each grid rated at 16 amps. The lower grid would supply one controller and five disk arrays (1 + 1.8 + 1.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring and Power Power Cord Routing Notes Review this power cord routing information before installing a StorageTek 9176 or D173 rackmount device (controller tray or drive tray).
.............................................................................. Rackmount Considerations The rackmount cabinet’s PDU supplies power for the left or the right sides of each redundant device’s DC power supply. The 9176 Disk Controller, 9170 Disk Array, and D173 Disk Controller Array have their own power cord.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements Environmental Requirements 9176 Disk Controller Table 10 lists the environmental requirements for the 9176 controller tray. Table 10 Condition Controller Tray Environmental Requirements Range Requirement Below Sea Level Above Sea Level Operating 30.5 m (100 ft.) 3,048 m (10,000 ft.) Storage 30.5 m (100 ft.) 3,048 m (10,000 ft.) Transit 30.5 m (100 ft.
.............................................................................. Disk Controller Airflow Figure 6 shows the controller tray airflow. Make sure your installation site will allow adequate ventilation of the rackmounted controller tray during operation. Important: Allow adequate clearance behind controller trays to maintain a safe operating temperature between 10° C and 40° C (50° F and 104° F).
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements 9170 Disk Array and D173 Disk Controller Array Table 11 lists the environmental requirements for the 9170/D173 drive trays. Table 11 Condition Drive Tray Environmental Requirements Range Requirement Below Sea Level Above Sea Level Operating 30.5 m (100 ft.) 3,000 m (9,840 ft.) Storage 30.5 m (100 ft.) 3,000 m (9,840 ft.) Transit 30.5 m (100 ft.
.............................................................................. 9170/D173 Drive Tray Airflow Figure 7 shows the StorageTek 9170 and D173 airflow. Make sure your installation site will allow adequate ventilation of the drive tray during operation. Refer to the StorageTek 9170 or D173 User’s Guides, for specific requirements when placed inside of a rackmount cabinet.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Tray and Drive Tray Connectors Controller Tray and Drive Tray Connectors This section provides an overview of the controller tray and drive tray connectors, which you will use to cable either type of tray to your storage subsystem. The controller tray has three types of interface connectors (Figure 8). interface connectors: Fiber Channel (FC) (fiber optic or copper wire).
.............................................................................. Host Interface Connectors The controller tray contains four host interface cards. The cards can be GBIC (gigabit interface card) or DB-9 cards. A GBIC card contains a pair of GBIC interface connectors, which interface the controller to fibre optic or copper fibre host cables. A DB-9 card contains a pair of DB-9 interface modules, which interface the controller to copper fibre host cables.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Tray and Drive Tray Connectors Drive Interface Connectors The controller tray contains four GBIC or DB-9 host interface cards aka drive minihub cards. Figure 10 shows DB-9 cards in each drive interface card slot. Each card contains two GBIC or DB-9 connectors respectively and supports 8-bit and 16-bit interface protocol. Each interface card represents a single drive channel.
.............................................................................. NOTE The photograph below shows the D173’s host (two per subsystem or one redundant connection) and drive interface connectors (which support up to 30 drive modules). Secondary (Diagnostic) Interface Connectors The controller tray provides an RS-232 (serial) and an Ethernet connection to each controller (Controller A and Controller B) for use in diagnostics, troubleshooting, and special configurations.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9170-001 Interface Components 9170-001 Interface Components The 9170-001 drive tray has four interface connectors— two on each Channel Card Module (see Figure 12). The 9170 FC cables use HSSDC to HSSDC connectors to route data, providing copper fibre cables’ performance and reliability to the 9170 Disk Arrays.
.............................................................................. Controller and Array Cable Requirements Table 12 lists the cable requirements for controller and drive cable connections. For performance sake of the interface card, you can use either fibre optic or twisted-pair copper cable for host connections, depending on your host to storage subsystem distances. Fibre Channel copper cables are used to make the 9170 drive connections.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Hardware Installing the Hardware Host Adapters You can connect hosts to the controller tray using either a single-or dual-bus configuration (Figure 13). In a single-bus configuration, each host connects to only one controller. In a dual-bus configuration, each host connects to both controllers.
..............................................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Hardware Other Hardware Additional hardware you will need to install depends on whether you use the host-agent method (Figure 14 and Figure 16) or the direct-manage (Figure 15 and Figure 17) method to manage the Disk storage subsystem.
.............................................................................. Host-Agent Manage Method Use the client software from a management station to manage storage arrays through the software agent, which is installed on a host connected to the storage arrays using a Fibre Channel I/O path.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Hardware Direct-Manage Method Use the client software from a management station to manage storage arrays through direct Ethernet connections to the controllers.The host machine is connected to the storage arrays using a Fibre Channel I/O path.
.............................................................................. StorageTek Disk Subsystem comparisons To assist with your purchasing decisions, use these parameters and consult with your local area sales team representatives to plan the solution that is best for your operating environment.
A Feature Codes ■ Program Configuration Engineering’s Program Configuration Document (PCD) defines the applicable Configuration Control Documents (CCD) that are required to define the StorageTek 9176 and D173 Disk Subsystems, and provide the physical and logical intregration rules of the multiple hardware and software models. All of these documents can be found on the KnowledgeMap, which maintains the latest releases of these documents. Other documentation released by engineering include: Document No.
Program Configuration g. Copper or Shortwave (fibre optic) GBIC included in Host attach kits h. Cables for host attach kits are ordered separately i. Every controller must have at least one 9170-001 Disk Array j. Maximum of ten, 9170 Disk Arrays (up to 100 (36, 72 or 180 Gigabyte) drive modules) k. Battery Backup Unit (BBU) supplied l. 19 inch rackmount cabinet installation available m. Height = 4U n. One Storage partition is supplied. Ordered separately, feature code P1T4 is Storage Partition 1-4.
Program Configuration j. Maximum of twenty, 9170 Disk Arrays (up to 200 drives) - 36, 72 or 180 Gigabytes k. Battery Backup Unit (BBU) supplied l. 19 inch rackmount cabinet installation available m. Height = 4U n. One Storage partition is supplied. P1T4 (Storage Partition 1-4) and P5T8 (Storage Partition 5-8) must be ordered separately.
Program Configuration k. 19 inch rackmount cabinet installation available l. Height = 3U for the Disk Controller Array and each 9170 expansion unit m. One Storage partition is supplied. Ordered separately, feature code PT02 is for 1-2 storage partitions. P1T4 is for Storage Partition 1-4. If you increase the number of attaches using network hardware (hubs, switches, etc..), P5T8, Storage Partition 5-8 would be the additional feature code ordered. A form is available with more (up to 16 (PT16)).
Program Configuration • • • • • Slide assy feature codes are for Servers or other appliances that need to be pulled out. Rail assy feature codes are for appliances other than the 9176/9170. The CBNT M03 is connected to the AC power source by a NEMA L6 power cords on all North American installations. The CBNT M03 when shipped with an International power cords and will require the local StorageTek office to provide the power connection for all International installations.
Program Configuration 9176 Hardware and Software Features FeatureCodes 44 DESCRIPTION Opt/ Pick one 9176 001 9176 002 SP02 ADDITIONAL STORAGE PROCESSOR CARD P X NA P1T4 STORAGE PARTITION 1 THRU 4 O X X P5T8 STORAGE PARTITION 5 THRU 8 O X X PT16 STORAGE PARTITION 9 THRU 16 O X X M03R CBNT M03 RACKMOUNT P X X AR01 ADJUSTABLE RACK RAILS P X X FeatureCodes DESCRIPTION/HOST ATTACHMENT Opt/ Req 9176 001 9176 002 SPC1 1 SUN PCI COPPER ATTACH W/CARD O X X SPC2 2 SUN P
Program Configuration MN5002 FeatureCodes DESCRIPTION/HOST ATTACHMENT Opt/ Req 9176 001 9176 002 SPG5 5 SUN PCI SHWV ATTACH W/CARD O X SPG6 6 SUN PCI SHWV ATTACH W/CARD O X SPG7 7 SUN PCI SHWV ATTACH W/CARD O X SPG8 8 SUN PCI SHWV ATTACH W/CARD O X SPGA 1 SUN PCI SHWV ATTACH WO/CARD O X X SPGB 2 SUN PCI SHWV ATTACH WO/CARD O X X SPGC 3 SUN PCI SHWV ATTACH WO/CARD O X X SPGD 4 SUN PCI SHWV ATTACH WO/CARD O X X SPGE 5 SUN PCI SHWV ATTACH WO/CARD O X SPGF 6 SUN P
Program Configuration 46 Opt/ Req 9176 001 9176 002 3 SUNSBUS SHWV ATTACH W/CARD O X X SSG4 4 SUNSBUS SHWV ATTACH W/CARD O X X SSG5 5 SUNSBUS SHWV ATTACH W/CARD O X SSG6 6 SUNSBUS SHWV ATTACH W/CARD O X SSG7 7 SUNSBUS SHWV ATTACH W/CARD O X SSG8 8 SUNSBUS SHWV ATTACH W/CARD O X SSGA 1 SUNSBUS SHWV ATTACH WO/CARD O X X SSGB 2 SUNSBUS SHWV ATTACH WO/CARD O X X SSGC 3 SUNSBUS SHWV ATTACH WO/CARD O X X SSGD 4 SUNSBUS SHWV ATTACH WO/CARD O X X SSGE 5 SUNSBUS SHW
Program Configuration Opt/ Req 9176 001 9176 002 1 NT PCI SHWV ATTACH W/CARD O X X NTG2 2 NT PCI SHWV ATTACH W/CARD O X X NTG3 3 NT PCI SHWV ATTACH W/CARD O X X NTG4 4 NT PCI SHWV ATTACH W/CARD O X X NTG5 5 NT PCI SHWV ATTACH W/CARD O X NTG6 6 NT PCI SHWV ATTACH W/CARD O X NTG7 7 NT PCI SHWV ATTACH W/CARD O X NTG8 8 NT PCI SHWV ATTACH W/CARD O X NTGA 1 NT PCI SHWV ATTACH WO/CARD O X X NTGB 2 NT PCI SHWV ATTACH WO/CARD O X X NTGC 3 NT PCI SHWV ATTACH WO/CARD
Program Configuration DRIVE FEATURES CODES FOR 9170 Feature codes DESCRIPTION Opt/ Pick one 9170001 F185 5 18GB 10K FIBRE DRV O X F18A 10 18GB 10K FIBRE DRV O X F365 5 36GB 10K FIBRE DRV O X F36A 10 36GB 10K FIBRE DRV O X FP05 5 DRIVE FILLER PANEL O X FP10 10 DRIVE FILLER PANEL O X M02R CBNT M02 MOUNTING KIT P X M03R CBNT M03 RACKMOUNT P X AR01 ADJUSTABLE RACK RAILS P X Note: FP05 or FP10 are always needed when 10 drives have not been ordered.
Program Configuration FEATURE CODES MN5002 DESCRIPTION PART NUMBER/QTY O050 2-50M SC/SC DUPLEX OPT CBL 10800137 X2 O100 2-10M SC/SC DUPLEX OPT CBL 10800138 X2 O250 2-250M SC/SC DUPLEX OPT CBL 10800139 X2 O500 2-500 M SC/SC DUPLEX OPT CBL 10800140 X2 OA11 3-5M SC/SC DUPLEX OPT CBL 10800133 X3 OA12 3-10M SC/SC DUPLEX OPT CBL 10800134 X3 OA13 3-50M SC/SC DUPLEX OPT CBL 10800137 X3 OA14 3-100M SC/SC DUPLEX OPT CBL 10800138 X3 OA15 3-250M SC/SC DUPLEX OPT CBL 10800139 X3 OA16 3-5
Program Configuration FEATURE CODES DESCRIPTION PART NUMBER/QTY OA48 6-20M SC/SC DUPLEX OPT CBL 10800135 X6 OA51 7-5M SC/SC DUPLEX OPT CBL 10800133 X7 OA52 7-10M SC/SC DUPLEX OPT CBL 10800134 X7 OA53 7-50M SC/SC DUPLEX OPT CBL 10800137 X7 OA54 7-100M SC/SC DUPLEX OPT CBL 10800138 X7 OA55 7-250M SC/SC DUPLEX OPT CBL 10800139 X7 OA56 7-500M SC/SC DUPLEX OPT CBL 10800140 X7 OA57 7-30M SC/SC DUPLEX OPT CBL 10800136 X7 OA58 7-20M SC/SC DUPLEX OPT CBL 10800135 X7 OA61 8-5M SC/SC DU
Program Configuration FEATURE CODE DESCRIPTION PART NUMBER HH33 4-10M HSSDC/HSSDC(COPPER) 10083570 X4 HH41 5-3M HSSDC/HSSDC (COPPER) 10083586 X5 HH42 5-5M HSSDC/HSSDC(COPPER) 10083569 X5 HH43 5-10M HSSDC/HSSDC(COPPER) 10083570 X5 HH51 6-3M HSSDC/HSSDC(COPPER) 10083586 X6 HH52 6-5M HSSDC/HSSDC(COPPER) 10083569 X6 HH53 6-10M HSSDC/HSSDC(COPPER) 10083570 X6 HH61 7-3M HSSDC/HSSDC (COPPER) 10083586 X7 HH62 7-5M HSSDC/HSSDC(COPPER) 10083569 X7 HH63 7-10M HSSDC/HSSDC(COPPER) 100835
Program Configuration FEATURE CODE DESCRIPTION PART NUMBER DH32 4-5 METER DB9/HSSDC COPPER CBL 10083561 X4 DH33 4-10 METER DB9/HSSDC COPPER CBL 10083562 X4 DH34 4-30 METER DB9/HSSDC COPPER CBL 10083565 X4 DH41 5-3 METER DB9/HSSDC COPPER CBL 10083585 X5 DH42 5-5 METER DB9/HSSDC COPPER CBL 10083561 X5 DH43 5-10 METER DB9/HSSDC COPPER CBL 10083562 X5 DH51 6-3 METER DB9/HSSDC COPPER CBL 10083585 X6 DH52 6-5 METER DB9/HSSDC COPPER CBL 10083561 X6 DH53 6-10 METER DB9/HSSDC COPPER CBL
Index Numerics 9170 weight 15 9176-001 5, 6 9176-002 6 A address card CRU weight 15 air conditioning 23 altitude 25 altitude specifications 23 automatic power recovery 17 auto-ranging power supplies 19 B back cover (deskside) removing 21 battery backup 6 bels, sound power 23 Btu (British thermal units) 23 C cabinet info 11 cable connections 30 Fibre Channel 32 length 32 VHDCI 19 cable connectors 10 changing temperature 23 circuit breaker 17 cluster server hardware installation 33 host adapters installation
voltages 18 weight 15 E earth ground 17, 18 electrical circuit breakers 17 copper wire signal 32 drive module requirements 18, 19 earth ground 17, 18 frequency 18 overload protection 17 single-phase wiring 17 site wiring 17 voltage 19 voltage interruptions 17 engineering web pages 2 ESM CRU weight 13, 15 Ethernet connector 30 F failover 4 fan CRU weight 13, 15 feature codes 6 fiber optic cable length 32 Fibre Channel cable requirements 32 data transfers 32 host ID 30 interface connector 30 frequency.
PCD 6 performance 7 planning 9 platforms 1 power interruptions 17 loss and recovery 17 overload protection 17 requirements 18, 19 voltage requirements 19 Power Source 12 power supply CRU auto-ranging voltage 19 voltages 19 weight 13, 15 power-up recovery sequence 17 pressure (sound) 23, 25 protocol for SCSI drive cables 19 R rackmount dimensions 14 drive module weights 15 RDAC 4 relative humidity 23, 25 RS-232 connector 30 S SCSI cable, maximum length 19 interface 30 sea level temperature 25 servers 1 short
World Headquarters Storage Technology Corporation One StorageTek Drive Louisville, Colorado 80028 USA Phone: 1.800.786.7835 Fax: 719.536.