Quick Start Manual

Downdraft Specifications 8
Electrical Requirements
W
olf downdraft ventilation systems require a separate,
grounded 120 V AC, 60 Hz power supply. The service
should have its own 15 amp circuit breaker, and a
grounded 3-prong receptacle should be located within
reach of the 2
1
/2' (.8 m) power cord. The specific location
of the outlet is not critical, as long as it is within reach of
the power cord that is located mid-way, top and bottom,
on the right side of the downdraft. Certain installations
may require that the electrical supply be placed in an
adjacent cabinet.
IMPORTANT NOTE: If model DD30 is to be installed in a
30" (762) wide cabinet, model DD36 in a 36" (914) wide
cabinet or model DD45 in a 45
1
/2" (1156) wide cabinet, the
electrical outlet cannot be located on the back wall of the
cabinet. The outlet can be placed in an adjacent cabinet
within reach of the power cord. An access hole for the
power cord must be drilled in the cabinet wall.
IMPORTANT NOTE: A ground fault circuit interrupter
(GFCI) is not recommended and may cause interruption of
operation.
You must follow all National Electrical Code regulations. In
addition, be aware of local codes and ordinances when
installing your service.
The electrical outlet must be checked by a qualified
electrician to be sure that it is wired with the correct
polarity. Verify that the outlet provides 120 V AC and is
properly grounded.
Do not use an extension cord or two-prong adapter.
Electrical ground is required on this appliance. Do not
remove the power supply cord ground prong.