MINIMUM CLEARANCES
WALL INSTALLATIONS
M
inimum clearances for gas rangetops
without a ventilation hood:
Surface Burners or Griddle (G) Models:
30" (762) minimum vertical distance from
countertop to combustible materials above
the rangetop.
Charbroiler (C) Models: 36" (914) minimum
vertical distance from countertop to
combustible materials above the rangetop.
ISLAND | PENINSULA INSTALLATIONS
Minimum clearances to combustible
surfaces:
Island Installations: Minimum 12" (305)
clearance to rear wall that rises above the
countertop.
Peninsula Installations: Minimum 6" (152)
clearance to side walls and minimum 12"
(305) clearance to rear wall that rises above
the countertop.
Refer to the Installation Specifications
illustrations for your model on pages 8–9 for
the exact rough opening dimensions.
7
Dimensions in parentheses are in
millimeters unless otherwise specified.
INSTALLATION INSTRUCTIONS
Failure to locate the rangetop without
the proper clearances will result in a fire
hazar
d.
RISER REQUIREMENTS
I
nstallations against a combustible surface:
The 10
1
/2" (267) riser is required for all gas
rangetops in non-island applications installed
against a combustible surface.