INSTALLATION INSTRUCTIONS
GAS SUPPLY REQUIREMENTS
IMPORTANT NOTE:
The supply line must
be equipped with an approved external gas
s
hut-off valve located near the cooktop in an
accessible location. Do not block access to the
shut-off valve. Refer to the illustration below.
The inlet pressure to the regulator should be
a
s follows for operation and checking the regu-
lator setting:
Natural Gas:
Set pressure 5" (12.5 mb) WC,
supply pressure 7–14" (17.5–34.9 mb) max.
LP Gas:
Set pressure 10" (25 mb) WC,
supply pressure 12–14" (29.9–34.9 mb) WC.
LINE PRESSURE TESTING
T
esting above .5 psi (3.5 kPa) 14" (34.9 mb)
WC (gauge):
The cooktop and its individual
shut-off valve must be disconnected from
t
he gas supply piping system during any
pressure testing of that system at test pres-
sures greater than .5 psi (3.5 kPa).
Testing below .5 psi (3.5 kPa) 14" (34.9 mb)
WC (gauge) or lower:
The cooktop must be
isolated from the gas supply piping system
by closing its individual manual shut-off
valve during any pressure testing of the gas
supply piping system at test pressures
equal to or less than .5 psi (3.5 kPa).