GAS SUPPLY REQUIREMENTS
GAS MANIFOLD PRESSURE
F
or Natural Gas:
S
tandard orifices
are set for 5" (12.5 mb) WC (water column).
A natural gas pressure regulator is
i
nstalled.
For Propane (LP) Gas:
Standard orifices
are set for 10" (25 mb) WC (water column).
A propane gas pressure regulator is
installed.
Gas Supply Pressure:
For checking the
regulator setting, the maximum line
pressure for natural and propane (LP) gas:
14" (34.9 mb) WC; .5 psi (3.5 kPa). Minimum
line pressure for natural gas: 7" (17.5 mb)
WC. Minimum line pressure for propane
(LP) gas: 11" (27.4 mb) WC.
Gas Supply Regulator:
To control and
maintain a uniform gas pressure in the gas
manifold, the unit must be used with a gas
pressure regulator. The burner orifices, etc.
are sized for the gas pressure delivered by
the supplied regulator. Do not remove the
regulator.
GAS LEAK TESTING
U
se a brush and liquid detergent to test all gas
connections for leaks. Bubbles around connec-
tions will indicate a leak. If a leak appears, shut
o
ff the gas valve and adjust connections. Then
check connections again. Clean all the deter-
gent solution from the rangetop.
12
WOLF SEALED BURNER RANGETOP
Never test for a gas leak with a match or
other flame.
The maximum gas supply pressure to
the regulator should never exceed 14"
(34.9 mb) WC; .5 psi (3.5 kPa).