Portable Generator User Manual

– 54 –
6.TROUBLE SHOOTING
No output power or Low output
Engine start
Engine start
Change INV C/U
Resistance value of the stator windings for reference
Surrounding temperature 20
Red
White
Blue
Measured resistance value
Generator
(Refer to the table below)
Measure the resistance value between
Abnormal
Change the alternator
Red-white
White-blue
Red-blue
)
Low or
None
Within the rating
Low or High
Remove the electric
equipment that is connected
Stop the engine, and reset the overload warning
Confirm the engine revolutions
(Turn of the APS switch)
Correct revolution 35503650rpm
Go to the engine
malfunction section.
engine check
(refer to p. 56)
RG3200i
RG3200iS
RG2800i
RG2800iS
Wire Color
2.84.0
Red – White
Unit: Ohms (Ω)
0.81.1
White – Blue
0.81.1
Blue – Red
Voltage Spec.
220, 230, 240
110, 120
110, 120
RG4300i
RG4300iS
2.1
0.81.1
2.84.0220, 230, 240
2.1
2.84.0220, 230, 240
2.1
110, 120 0.5
0.5
0.5
Voltage display is :
No
Within the rated range
Out of the
rated range
Overload warning- "O_Load" is displayed
Yes