11.12.4 Control of the condenser fan (SR 10-100)
A temperature probe T2 is located on the discharge side of the condenser. The condenser fan is activated (ON) when
the T2 temperature is higher than FANon setting (standard 35°C / 96°F) and led is ON.
Condenser fan stops at T2 temperatures 5°C / 10°F lower than FANon setting (standard 30°C / 86°F).
11.12.5 Control of the drain solenoid valve
Drain solenoid valve is activated (ON) for Ton seconds (standard 2 seconds) every Toff minutes (standard 1 minute).
Led shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button .
11.12.6 How to change operating parameters SETUP menu
The setup menu can be used to change the dryer’s operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON press button for at least 3 seconds to enter the setup menu.
Access to the menu is confirmed by led and flashing (first parameter of menu).
Keep pressed and use arrows to change the value. Release the button to confirm the value.
Press shortly to skip to following parameter.
Press to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Display
Description
Limits
Resolution
Standard
setup
Synchronous flashing
led + led
(SR 10-100)
FANon : condenser fan activation
(ON) temperature
31 … 40 °C or
88 … 104 °F
1 °C
or
2 °F
35
or
96
Synchronous flashing
led + led
Ton drain time ON : time ON
condensate drain valve
1 … 10 sec
1 sec
2
Non-Synchronous flashing
led + led
ToF - drain time OFF : pause time
for condensate drain valve
1 … 20 min
1 min
1
NOTE : parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is
the highest limit.
11.13 Electronically level-controlled Sullimax condensate drain
The electronically level-controlled Sullimax condensate drain boasts a special condensate management which ensures
that condensate is discharged safely and without an unnecessary loss of compressed air. This drain has a condensate
collection container in which a capacitive sensor continuously monitors the liquid level. As soon as the switching level
is reached, the capacitive sensor transmits a signal to the electronic control and a membrane solenoid valve opens to
discharge the condensate. The Sullimax closes before compressed air emerges.