DAILY:
• Check whether the dew point indicated on the electronics is correct.
• Ensure that the condensate drain system functions properly.
• Make sure that the condenser is clean.
EVERY 200 HOURS OR MONTHLY
• Clean the condenser using an air jet (max. 2 bar / 30 psig) inside out. Make
sure not to damage the aluminium lamellae of the cooling package.
• Finally, verify the operation of the device.
EVERY 1,000 HOURS OR ANNUALLY
• Verify all screws, clamps and connections of the electric system to make sure that they are
fastened securely. Check the device for broken and ruptured cables or cables without
insulation.
• Check the refrigeration cycle for signs of oil and refrigerant leaks.
• Measure the current strength and note it down. Ensure that the read values are within the permissible
limit values, as indicated in the specification table.
• Check the hose lines of the condensate drain and replace them, if required.
• Finally, verify the operation of the device.
EVERY 8,000 HOURS
• Replace Sullimax Service Unit.