DAILY:
Check whether the dew point indicated on the electronics is correct.
Ensure that the condensate drain system functions properly.
Make sure that the condenser is clean.
EVERY 200 HOURS OR MONTHLY
Clean the condenser using an air jet (max. 2 bar / 30 psig) inside out. Make
sure not to damage the aluminium lamellae of the cooling package.
Finally, verify the operation of the device.
EVERY 1,000 HOURS OR ANNUALLY
Verify all screws, clamps and connections of the electric system to make sure that they are
fastened securely. Check the device for broken and ruptured cables or cables without
insulation.
Check the refrigeration cycle for signs of oil and refrigerant leaks.
Measure the current strength and note it down. Ensure that the read values are within the permissible
limit values, as indicated in the specification table.
Check the hose lines of the condensate drain and replace them, if required.
Finally, verify the operation of the device.
EVERY 8,000 HOURS
Replace Sullimax Service Unit.