• Ensure that the fan runs properly – wait for the first interventions.
• Wait until the dew point remains stable.
• Slowly open the air inlet valve.
• Slowly open the air outlet valve.
• Slowly close the central bypass valve of the system (if installed).
• Check the pipes for air leakage.
• Ensure the proper functioning of the condensate drain cycle (wait for the first condensate discharges).
Note!
A DewPoint included in the green operating area of the electronic controller is correct according to the
possible working conditions (flow-rate, temperature of the incoming air, ambient temperature, etc.)
During the operation, the refrigerating compressor runs continuously. The dryer needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
9.3 Shut down and restart
Shut down (see Section 11.1 "Control panel")
• Ensure that the dew point temperature indicated on the electronic control unit is stable.
• Interrupt the compressed-air supply.
• After a few minutes, stop the dryer by switching off the main switch on the control panel (pos. 1).
Restart (see Section 11.1 "Control panel")
• Make sure that the condenser is clean
• Check whether or not voltage is applied at the dryer.
• Start the dryer by switching on the main switch on the control panel (pos. 1).
• Ensure that the electronic control unit is switched on.
• Wait a few minutes and then check, whether or not the dew point temperature indicated on the
electronic control unit is stable and whether or not the condensate is drained off at regular intervals.
• Establish the compressed-air supply.
During the operation, the refrigerating compressor runs continuously. The dryer needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
Note!
A DewPoint included in the green operating area of the electronic controller is correct according to the
possible working conditions (flow-rate, temperature of the incoming air, ambient temperature, etc.)
Note!
The dryer must not be started up more than six times an hour. Wait at least five minutes prior to every
restart.