The dryer continuously
drains condensate.
SULLIMAX drainer is dirty (see SULLIMAX MANUAL)
Water within the line.
The dryer doesn't start - see specific point.
Where installed - Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn’t drain the condensate - see specific point.
DewPoint too high - see specific point.
Where installed - The
HPS high-pressure
switch has been
activated.
Check which of the following has caused the activation :
1. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation.
2. The condenser is dirty clean it.
3. The condenser fan doesn’t work - see specific point.
Reset the pressure-switch pressing the button on the controller itself - verify the dryer for correct operation.
The HPS pressure switch is faulty - contact a refrigeration engineer to replace it.
Where installed - The
LPS low-pressure switch
has been activated.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
The pressure switch restores automatically when normal conditions are restored - check the proper operation
of the dryer.
Where installed - The
TS safety thermo-switch
has been activated.
Check which of the following has caused the activation :
1. Eccessive thermal load restore the standard operating conditions.
2. The inlet air is too hot - restore the nominal conditions.
3. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation.
4. The condenser unit is dirty - clean it.
5. The fan doesn’t work - see specific point.
6. There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
Reset the thermo-switch by pressing the button on the thermo-switch itself verify the correct operation of
the dryer.
The TS thermo-switch is faulty - replace it.
DMC14 - The LED of the
instrument is on or
flashes to indicate alarm
situations.
The LED flashes because the DewPoint is too high see specific point.
The LED flashes because the DewPoint is too low - see specific point.
The LED flashes because the probe is faulty or interrupted, the instrument displays the messagePF(Probe
Failure) replace the probe.
The dryer doesn’t drain
the condensate.
The condensate drain service valve is closed - open it.
Verify the electric wiring.
The DewPoint is too low - the condensate is frozen - see specific point.
SULLIMAX drainer is not operating correctly (see SULLIMAX MANUAL)