PARAMETER TABLE
Item
Description
Setting Range
Default
Unit
User Menu
St
Temperature set-point
Low set-point~High set-point
4
/
Po
Administrator menu password
00~99(Default password is 55 and
unchangeable)
00
/
Administrator Menu
C1
Differential
0.5~9.0
4
/
1~20
C2
Compressor start delay between
last switch-off and the successive
switch-on
0~60
5
min
C3
Compressor start delay after
switch-on of the device
0~90
5
min
C4
Calibration temperature 1.
Temperature value added to the
value read by cabinet sensor
-10.0~10.0
0.0
/
-20~20
C5
Low set-point. Minimum possible
set-point
-50 ~Temperature set-point
-2
/
-58 ~Temperature set-point
C6
High set-point. Maximum possible
set-point
Temperature set-point ~ -85
22
/
Temperature set-point ~ -185
C7
Maximum standby time after
compressor start delay
0~90
0: Disabled
9
min
C8
Minimum compressor on time
0~90
0: Disabled
0
min
d1
Evaporator sensor options
0: Disable
1: Enable
0
/
d2
Calibration temperature 2. The
temperature value added to the
value read by the evaporator
sensor.
-10.0~10.0
0.0
/
-20~20
d3
Defrost counting type
0: Compressor operating time
1: Controller power-on time
1
/
d4
Defrost interval time
0~90
0: Disable defrost
2
hour
d5
Display during defrost
0: Displays cabinet temperature;
1: Displays dEF during defrost and d9,
displays cabinet temperature after d9
elapses;
2: Displays dEF during defrost and
dripping;
3. Displays cabinet temperature at
defrost start during defrost and dripping.
4.
2
/
d6
Maximum defrost duration
1~90
25
min