Product Manual
SUMPRO
®
Battery Back-Up
OPERATION MANUAL
Dated: 08/08/2014
Document Name: SUMPRO_100_OM.indd
Page 5 of 12
Register your product at www.ionproducts.net
6. Within 30 seconds, connect the positive (+) red
battery lead (red) to the positive (+) post.
Note: Make sure all battery connections are properly
tightened to 75 pound inches.
7. Close Unit
Close and secure the battery enclosure lid, so that
children cannot tamper with the unit.
8. Plug In The Pump
At this time you may plug your 115V pump into your
SUMPRO
®
unit, not exceeding the load limit of 12
amps or 1440 watts at any one time.
Note: If connecting a pump controller, such as the
Ion Genesis or Ion Endeavor, follow the installation
instructions in the controller manual. The controller
will be plugged into the SUMPRO
®
instead of the wall
outlet.
lIght and relay functIonS
After you have your SUMPRO
®
unit in operation, you
can check its status by looking at the system lights.
They should tell you everything you need to know
about the status of the unit.
1. Power – Green LED
a. Solid when AC Line In Voltage is deemed
present.
b. Off when AC Line In fault occurs.
2. Inverter – Red LED
a. Blinks when unit is running off inverter and
silence has NOT been pressed.
b. Solid when unit is running off inverter and
silence has been pressed.
c. Off when unit is operating off of AC Line
3. Alarm – Red LED
a. Blinks when alarm condition occurs and
silence has NOT been pressed
b. Solid when alarm condition occurs and
silence has been pressed
c. Off when no alarm condition is present
d. Alarm Contact – NC dry contact
i. Opens when either the Inverter LED or
Alarm LED are blinking
4. LCD Display - Displays all info that pertains to
current operating condition of the unit
teStIng the SyStem
To test the SUMPRO
®
, simply unplug it from the 115V
AC power to run your pump on battery power for a
short time. You can repeat this if you wish, but it is
not necessary. If your SUMPRO
®
unit works the rst
time it is sure to work time and time again. Be sure
that you remember to plug the unit back into the
receptacle after you have completed the test.
Note: New batteries are rarely fully charged.
Depending on the charge condition of the batteries
and the voltage from the utility company, it may take
up to 7 days for the batteries to be fully charged.
Sumpro
®
maIntenance
Your SUMPRO
®
unit has been designed to be virtually
maintenance free. Just make sure it is kept clean and
dry and that the unit is periodically tested in the auxiliary
mode.
Battery maIntenance
If you are using AGM maintenance free batteries, you
should visually inspect the batteries every six months
for swelling or leakage. For all other batteries, refer to
the manufacturer recommended battery maintenance
section of the battery being used.
Maintenance or replacement of batteries should be
performed or supervised by personnel knowledgeable
of batteries and the required precautions.
replacIng BatterIeS
Wear full eye protection and protective clothing.
When replacing the batteries, use the same type and
size batteries. See battery requirements (Page 2).
CAUTION: The electrolyte is a dilute sulfuric
acid that is harmful to the skin and eyes. It is
electrically conductive and corrosive. The following
procedures should be observed: