Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions
10
www.QuestProtect.com
sales@QuestProtect.com
7.1 Air Filter
TheQuestDualshipswithastandardMERV11efcientpleatedfabriclter.Thisshouldbechecked
everysixmonths.Thepleatedfabricltercangenerallybevacuumedcleanseveraltimesbeforeneeding
replacement.Operatingtheunitwithadirtylterwillreducedehumidiercapacityandefciencyandmay
causethecompressortocycleonandoffunnecessarily.Replacementlterscanbeorderedfromyourdealer
or by calling 1-800-533-7533.
8. Service
WARNING! Servicing the Quest Dual with its high pressure refrigerant system and
high voltage circuitry presents a health hazard which could result in death, serious
bodily injury, and/or property damage. Only qualied service people should service this
unit.
8.1 Technical Description
The Quest Dual uses a refrigeration system similar to an air conditioner’s to remove heat and moisture from
incoming air, and add heat to the air that is discharged. Hot, high pressure refrigerant gas is routed from
the compressor to the condenser coil. The refrigerant is cooled and condensed by giving up its heat to the
airthatisabouttobedischargedfromtheunit.Therefrigerantliquidthenpassesthroughalter/drierand
capillary tubing which cause the refrigerant pressure and temperature to drop. It next enters the evaporator
coil where it absorbs heat from the incoming air and evaporates.
Theevaporatoroperatesinaoodedcondition,whichmeansthatalltheevaporatortubescontain
liquidrefrigerantduringnormaloperation.Aoodedevaporatorshouldmaintainconstantpressureand
temperature across the entire coil, from inlet to outlet. The mixture of gas and liquid refrigerant enter the
accumulator after leaving the evaporator coil. The accumulator prevents any liquid refrigerant from reaching
the compressor. The compressor evacuates the cool refrigerant gas from the accumulator and compresses it
to a high pressure and temperature gas to repeat the process.
Quest Dual refrigeration system