Owner manual
12-1 1
Outdoor Discharge over temperature error
Indoor display
ሱلሱ
Outdoor error
Outdoor display
ሱ
ƻ
م
Outdoor Discharge over temperature
error
1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data
2. Troubleshooting procedure
Is the discharge over temperature
sensor error appeared again?
Terminate the service
NO
aŌer 30min ~ 1Hr
YES
Is the discharge over temperature
sensor error appeared again?
The condiƟon is too poor for air condiƟoner to
operate
Wait unƟl discharge temperature is decreased
Restart aŌer power oī
YES
Download the EEPROM data
Is the discharge over temperature
sensor error appeared again?
YES
Terminate the service
Terminate the service
NO
NO
Exchange the Outdoor PBA
Exchanged the Compressor
Restart aŌer power oī.