DC_link voltage sensor error
Indoor display
ሱلሱ
Outdoor error
Outdoor display
مሱ
DC_link voltage sensor error
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(A*V18***:CE101,CE102,CE103,A*V24***:CE001,CE002,CE003,CE004)) assembled in accordance
the specification? (Outdoor PBA)
4) Is the DC_link resistor(A*V18***:R104,R106,R107,R108,A*V24***:R004,R005,R006,R007) value is normal? (Outdoor PBA)
2. Troubleshooting procedur
e
Is the connected of reactor wire?
(PBA-Reactor)
Is the DC_link sensing voltage(R
104
or R004) is normal in operaƟon
mode?
Normal range (0.
2
Vdc~2
.
8Vdc)
YES
Exchange the Outdoor PBA
NO
Is the DC_link voltage (CE101 or
CE001) is normal in operaƟon
mode?
Normal range(280Vdc~320Vdc)
Check the power input
NO
YES
YES
Connect the reactor wire
NO
Restart aŌer power oī.
Start the operaƟon (cooling mode or heaƟng mode)
Exchange the Reactor
Is the reactor insulaƟon damaged?
YES
Exchange the Outdoor PBA
NO