Gas leak error
Indoor display
ሱلሱ
Outdoor error
Outdoor display
ممل
Gas leak error
1.Checklist :
1) Is the position of indoor Eva_in sensor normal?
2) Check the pipe crack
3) Check the EEV valve connection in Outdoor unit
4) Check the refrigerant was charged
2. Troubleshooting procedure
Is the gas leak error appeared
again?
YES
Terminate the service.
NO
YES
Is the posiƟon of indoor eva_in
sensor normal?
Restart aŌer power oī
Indoor sensor take the normal posiƟon
NO
Is the EEV valve connecƟon
normal?
Check the EEV valve operaƟon.
Connect the EEV valve.
NO
YES
aŌer 20minutes later
Is the EEV valve is operaƟon?
Check the sound of EEV valve aŌer
power on.
Change the EEV valve.
NO
Is the pressure of refrigerant
normal?
Check the pipe crack.
Fill up the refrigerant.
YES
NO
YES
Exchange the Indoor PBA
Exchange the Outdoor PBA