BASIC TECHNICAL INFORMATION FOR: SAMSUNG MAX MINI-SPLIT UNITS Distributed by: WWW.SUNLIGHTSUPPLY.
Distributed by: Samsung MAX 12,000 BTU Mini-Split Indoor Unit: #700550 (AQN12VFUAGM) Outdoor Unit: #700552 (AQX12VFUAGM) POWER VOLTAGE: Power Voltage: Control Voltage: Main Breaker Size: 208/230V - 1 Ph - 60 Hz DDC Fuzzy Logic 15 A LINE SIZES: “Liquid” (expanded gas) line: 1/4” Suction: 3/8” BOTH LINES MUST BE INSULATED SEPARATELY INTERCONNECT LENGTH: Maximum/Minimum Length: Vertical Lift: 50 feet / 10 feet 26 feet Note: Condenser can be above or below evaporator CHARGING: Unit is charged for: Additio
Distributed by: Samsung MAX 24,000 BTU Mini-Split Indoor Unit: #700554 (AQN24VFUAGM) Outdoor Unit: #700556 (AQX24VFUAGM) POWER VOLTAGE: Power Voltage: Control Voltage: Main Breaker Size: 208/230V - 1 Ph - 60 Hz DDC Fuzzy Logic 20 A LINE SIZES: “Liquid” (expanded gas) line: 1/4” Suction: 5/8” BOTH LINES MUST BE INSULATED SEPARATELY INTERCONNECT LENGTH: Maximum/Minimum Length: Vertical Lift: 98 feet / 10 feet 50 feet (Trap required at 26 ft.
Distributed by: Samsung MAX 36,000 BTU Mini-Split Indoor Unit: #700558 (AQN36VFUAGM) Outdoor Unit: #700560 (AQX36VFUAGM) POWER VOLTAGE: Power Voltage: Control Voltage: Main Breaker Size: 208/230V - 1 Ph - 60 Hz DDC Fuzzy Logic 30 A LINE SIZES: “Liquid” (expanded gas) line: 1/4” Suction: 5/8” BOTH LINES MUST BE INSULATED SEPARATELY INTERCONNECT LENGTH: Maximum/Minimum Length: Vertical Lift: 164 feet / 10 feet 98 feet (Trap required at 26 ft.
Distributed by: Samsung MAX Wired Controller (optional) Part: #700574 sub-PCB INSTALLATION INSTRUCTIONS • The sub-PCB installs inside a single MAX indoor unit (Part #700550, #700554 or #700558). It is required to connect and control an indoor unit with the Samsung wired controller (part #700578). • Provides 12V DC to the Samsung wired controller (part #700578). • Required to control MAX models with Samsung central control options (upper level control).
Distributed by: sub-PCB INSTALLATION INSTRUCTIONS (continued...) 2. Inside the unit, towards the bottom of the cabinet you will find a PCB wire harness. Gently pull this wire upward and out of the unit. 3. Connect the PCB to the PCB wire harness (a) and to the sub-PCB wire harness (b). NOTE: the sub-PCB wire harness is included with the wired controller. (a) (b) 4. Remove the protective tape (a) and slide all connected wires into the groove beside the sub-PCB mounting location (b).
Distributed by: sub-PCB INSTALLATION INSTRUCTIONS (continued...) 5. With the wired controller wires already installed, pull the wires through the front of the indoor unit. Cut the 2 small plastic connectors off the ends of the sub-PCB wire harness (the ends of the red/blue and yellow/orange wires). Connect F3/F4 and V1/V2 between the indoor unit and the wired controller as pictured below.
Distributed by: BASIC INSTALLATION TIPS SIZING Computer/Data Rooms: Basic sizing is 200-250 sq. ft. per 12,000 BTU/h. Commercial/Retail: Basic sizing is 400-450 sq. ft. per 12,000 BTU/h. Residential: Basic sizing is 550-600 sq. ft. per 12,000 BTU/h. LOW AMBIENT COOLING Computer/Data Rooms and Commercial: As standard, these units have a low ambient cooling capability down to 10ºF outdoor temperature.
Distributed by: BASIC INSTALLATION TIPS (continued...) R410A REFRIGERANT (continued...) The gauge connection on the Samsung units is a 5/16” male, so an adapter is required to connect a standard North American set of R410A gauges to the Samsung unit. UNIT LOCATION Indoor Unit: High Wall units should be located a minimum of 4ft from the ground.