User Manual

1. The emergency lighting unit should be installed indoors, out of direct sunlight and humidity.
It should not be installed in environment with temperatures higher than 40 degrees Celsius.
2. The unit should be stored in temperatures under 25 Degree Celsius and the battery should
be charged every 3 months to maintain its operational life.
3. Please always read the manual carefully prior to operating the unit for the saftest and most
effective use of the product.
Important Note on Using the Unit
Indication
Lights
Display Meaning
- A continuous orange light
- The orange light turns off
- A continuous green light
- Slow blinking green
light every 2 seconds
- Fast blinking green
light every 1 seconds
- A continuous red light
- The red light turns off
- A red light blinks three
times every 15 seconds
- A red light blinks four
times every 15 seconds
- A red light blinks five
times every 15 seconds
- The unit is receiving a normal AC power supply.
- The unit is not receiving an AC power supply.
- When pressing “OFF” to turn off the automatic battery
test system (Auto Test) from the remote.
- When pressing “ON” to turn on the automatic battery
test system (Auto Test) from the remote.
- The unit is performing a battery test (Auto Test).
- The battery is charging.
- The battery is fully charged.
- “Battery Fail” When the emergency light unit supply
backs up the lighting for less than 120 minutes, or less
than the time tested with a remote control.
- “Charging fail” When the battery charging system does
not charge, the charger does not cut off, the charging
circuit cuts off, but the battery charge decreases too
quickly.
- “Lighting Fail” When the system encounters an
abnormality in the lighting system, such as loose lighting
cables, broken bulbs, etc.
On/ Test
Indicators
AC
Charge/Fail