Instructions / Assembly

6
3. Uplift Testing: SunSky corrugated polycarbonate panels meet Uplift Test Criteria specified in UL 580 Test for Uplift Resistance of Roof
Assemblies (UL Class 90). Consult Palram Americas technical support for additional details if necessary.
Test Description
Roof Covering: Corrugated polycarbonate roof panels with 9 inch
spaced corrugations. The tested material comes in 0. 032" thick x 38"
width and 12 feet long.
Fastener: #12 - 14 x 1-1/4" Type 2 Structural Drilling
Fastener, carbon steel, zinc plate with 3/4" O. D. heavy
EPDM/galvanized washer.
Uplift Test Results
A buckled hip was visible during the test. The fasteners were in
place and no cracks or breaks were found in the SunSky panels. The
test assembly withstood all phases of testing for Class 90. The roof
assembly described in this report met the uplift test criteria specified
in UL 580 - Test for Uplift Resistance of Roof Assemblies. Note: The
buckled hip returned to the original shape after testing with no panel
damage or permanent deformation.
4. Purlin & Girt Spacing: Purlin and girt spacing are usually dictated by
overall design and engineering calculations along which the whole
structure is constructed. SunSky panels are installed at the same
purlin/girt spacing as the rest of the metal panels in the structure.
Verify that the installed SunSky panels will remain within the uniform load-supporting limits of deflection as observed by the
Evaluation Acceptance tests (see the “Uniform Load” diagrams and “Uplift paragraphs).
In case purlin/girt spacing of the metal-clad structure surpass the values depicted in the tables by a significant margin (especially
in multi-panel runs), a secondary support system, based on data in the above mentioned tables, should be prepared for the SunSky
skylight or side light.
When support spacing is marginally larger, on-site environmental conditions should be considered and acted upon.
Figure 8