Manual

SunTouch WarmWire  Installation Manual  13
STEP 6.12  If it was necessary to end a power lead at a junction box,
feed 14- or 12-gauge electrical wire from this box to the control box.
Tip:  If more than one cable was installed, label the power leads 
with a brief description as to which area they supply power. Use tape 
to label them “Cable  1,“Cable 2,”or “K itchen,“Bath, or similar.This will 
make  it easier to identify the leads later on. Take photos of the installa-
tion.  This will provide a useful record for any future needs.
Phase  7: Install the Control
STEP 7.1   Read and follow the instructions that come with the SunStat 
controls.
STEP 7.2  Refer to the wiring diagrams in this manual for different 
voltages and applications.
STEP 7.3  Install the electrical  b ox for the control, if this has not 
already been done.Connect the power leads from the cable (or the 
electrical wiring coming from junction boxes) to the “LOAD”side of 
the control. Connect the incoming power to the “LINE” side of the  con-
trol.Connect the sensor wires to the sensor terminals on the control.
Connect the ground leads from the system to the ground wire from 
the incoming power.
STEP 7.4  Install the control into its electrical box and turn the circuit 
breaker on to power the system. Test the system and control for 
several cycles. It should allow the heating  c ables to heat up correctly.
Note: Consider placing a loose tile over the sensor tip to simulate 
warming the floor and allow the sensor to register  this on the control.
STEP 7.5  Retain all instruction sheets and warranties.
Phase  8: Install the Floor  Coverings
STEP 8.1 Make a Final Inspection of the Installation.Inspect the installa-
tion very carefully for evidence of damage or missing sensor(s).
STEP 8.2  Select Type of Construction. Choose the best thin-set,thick-
set, or self-leveling mortar method for the application.See Appendix 1 
regarding final floor installation techniques. Consult with building pro-
fessionals and/or the factory if assistance is required.
STEP 8.3 Take Another Resistance Reading!After floor cover ings have 
been installed, take resistance readings of the cable again to make sure 
it has not been inadvertently damaged.This is very important to do.
Record these readings in the Cable and Sensor Resistance Log (page 6).
Phase  9: Install Insulation
Insulate under the subfloor for better performance and efficiency 
of the system.Refer to the Appendix 1 for diagrams and insulation  
recommendations.
Phase  10: System Operation
After all system components are in place and floor coverings installed,
briefly test the operation of the system but do not put  the system  
into full operation until the mortar materials are fully cured (typically 
one to four weeks).See the mortar manufacturers recommendations 
for the specific type of mortar used.
Many manufacturers of laminate  and wood flooring recommend a 
maximum of about 84°F (29°C) on the floor surface. Be sure to program 
the control accordingly.Consult the manufacturer regarding recom-
mended floor temperatures for the  flo oring being installed.
Energize the system. Operate the controls so that the system turns 
on the floor-warming cable. The control will normally indicate that 
power is  b eing supplied to the cable. It will take some time for the 
cable to warm up.Using a clamp-type ammeter (electricians normally 
carry these), pull the control out of the wall and determine whether the 
cables are pulling current, thus indicating they are working as intended.
Turn the system off after  NO MORE than 10 minutes of operation. Do 
not operate the system again until the flo or mortar is cured. Once the 
flooring is completely cured,the control can be used to operate the 
system for many  years to come.
STEP 7.3
STEP 7.4