Manual

14 SunTouch WarmWire Installation Manual
Troubleshooting Guide
If not qualified to perform electrical installations,it is strongly recommended that a qualified,licensed electrician 
be hired to install the heating cables and related electrical components. If problems with the system arise, please 
consult the troubleshooting guide b elow.Any troubleshooting work should be done with the power removed 
from the circuit,unless otherwise indicated.Call the factory or see www.suntouch.com for further assistance.
Problem
Cable resistance measure- 
ment is outside the range  
printed on the nameplate  
label.
Floor does not get warm.
Floor heats continuously.
Floor temperature shows  
“HI” or may show tempera- 
ture over 100°F.
Control is not working 
correctly.
Control is not working 
at all.
GFCI conflicts and 
false-trips.
Possible Cause
An analog ohmmeter (using a moving  
needle) was used to take the reading.
If measurement shows an open or short 
circuit, the cable has been damaged.
If measurement is just a little low or high, room 
temperature has affected the resistance.
The resistance measurement could be from 
more than  one cable wired in series, or  wired 
in parallel.Either will provide false resistance  
readings.
The ohmmeter may be set to the wrong  
scale. For instance, the 200 K ohms scale 
measures up  to 200,000 ohms.
Cable has b een damaged.
GFCI has tripped, indicated by a light on the 
control or “GFCI TRIP”.
Incorrect voltage  supplied,or mismatched  
electrical components used.
Concrete slab floor.
Cables are wired in series” or daisy chained”
(end-to-end).
Incorrect wiring. The control was “bypassed”
when it was wired to the power supply.
Defective control.
Floor sensor is not wired properly,or is located 
incorrectly.
If a programmable control, the programming 
may be incorrect.
Incorrect voltage  supplied,or mismatched  
components used.
Floor sensor is not wired properly,or is not 
working properly.
Loose connection(s)  on line side and/or load 
side of control.
Defective control.
No power is supplied.
Floor sensor is not wired properly,or is not 
working properly.
Defective control.
More than one GFCI on the circuit.
An electric motor or a ballasted light source is 
sharing the circuit with the cable(s).
Solution
Obtain a digital ohmmeter able to read 0 to 20,000 ohms and 
remeasure the resistance.
Record resistances between all wires and  contact the manu- 
facturer.
Make the room temperature 65°–75°F, or contact the manu- 
facturer.
Make sure resistance measurements are for only one cable at  
a time. When connecting more than one cable to the control,
multiple cables must be wired in parallel (i.e.,black to black,
white to white).
The ohmmeter should typically be set to the 200 ohms scale,with  
the exception of cables having a rating above 200 ohms on their  
nameplate label. If the resistance reading is outside the range  
printed on  the nameplate label,contact the manufacturer.
Measure cable resistance. Check for both open circuit”and short 
circuit” as detailed earlier in this manual. I f damaged, record  
resistances between all wires and contact the manufacturer.
Check for loose wire connections. Reset the GFCI  on the control  
or circuit  break er. If it trips again,check for a short circuit in the  
cable as detailed earlier in this manual.If cable is damaged,
record resistances between all wires and contact the manufacturer.
If cable is not damaged, replace the GFCI control.Also see “GFCI  
conflicts”below.
Measure “line”voltage, 120V cables have black and white leads.
240V cables have black and blue leads.
Surface temperatures rise slowly in a slab. If, after 5 to 8 hours of  
heating, the floor is not warmer to the touch,check for cable dam- 
age (see “Cable has been damaged” above). Measure “load  
voltage/amperage to cable.
Multiple cables must be connected in “parallel” (or black-to-black,  
white-to-white).
Make sure wiring connections are correct. Consult the wiring  
diagram on  the back of the control, the  instructions that came 
with the control,or the wiring diagrams in Appendix 2.
Return control to dealer for replacement.
Make sure only one floor sensor is connected to the control.  
Also see “Sensor is loose or broken above.
Carefully read and follow control programming instructions.
Test voltage, verify parts. See “Incorrect voltage supplied” above.
Make sure only one floor sensor is connected to the control.  
Also see “Sensor is loose or broken above.
Remove and reinstall the wire nuts at each connection.Make sure 
the wire  nuts are tight. Check all connections back to the breaker.
Return control to dealer for replacement.
Check circuit breaker. Measure voltage  at the control. Check all  
connections between breaker and control.
Make sure only one floor sensor is connected to the control.  
Also see “Sensor is loose or broken above.
Return control to dealer for replacement.
GFCI units sometimes trip when there is nothing wrong with the 
equipment on the circuit, but when there is  more than one GFCI.  
Reroute power to avoid having more than one  GFCI on the circuit.
Electric motors and other electrical devices can cause a GFCI to  
false-trip. Run a dedicated circuit to the floor-warming system.