Manual

4 SunTouch WarmWire Installation Manual
Phase  2: Preparation
CAUTION!
As with any electrical product, care should be taken to guard against the 
potential risks of fire,electric shock, and injury to persons. The following 
cautions must be observed:
NEVER cut the heating cable. The 10-ft. power lead may be cut shorter if 
necessary,but never removed from  the heating cable.
NEVER use nails, staples, or similar to fasten the heating cable to the
floor.
NEVER bang a trowel or other tool on the  c able. Be careful not to nick,
cut, or pinch the cable causing it to be damaged.
NEVER install the cables under cabinets or other built-ins.Excessive heat 
will build up under these items and cause damage.
NEVER install the cable in any walls, over walls or partitions that  extend 
to the ceiling,or in closets.
NEVER extend the heating portion of the cable beyond the room or 
area in which it originates.
NEVER attempt to repair a damaged cable. Contact  the factory for assis-
tance.
NEVER overlap  heating cables.Dangerous overheating can occur.
NEVER allow a power lead or sensor wire to cross a heating cable;dam-
age could result.
NEVER embed the cables in adhesives  intended for laminate or vinyl 
flooring.Cables must be completely embedded in cement-based 
polymer-modified mortar.
NEVER apply the wrong voltage to a cable.Damage can result.
NEVER use 1” spacing.
ALWAYS completely embed the heating wire and factory splice
in mortar.
ALWAYS maintain a minimum of 2” spacing between cables.
ALWAYS use copper only as supply conductors to the control and the 
cable.Do not use aluminum.
ALWAYS test the cable resistances and record them in the Cable and 
NEVER bang a trowel or other 
tool on the heating c able.
NO!
Always completely embed the 
factory splice and all heating wire 
in mortar. NEVER bend the splice 
or place any part of it in the wall 
or through the floor.
Example 1.  There are 
40 sq. ft.of bathroom 
area to be warmed with 
120 VAC. The cable is to 
be spaced at 2-1/2”to 
provide 12 watts/sq. ft.,
providing comfortable 
warmth across  the floor 
area. As seen in Table 
1, use Model Number 
120040WD.
Example 2.  There are 
270 sq. ft.of kitchen and 
dining area to be warmed 
with 240 VAC. The cable is 
to be spaced at 3” to pro-
vide 10 watts/sq.ft., pro-
viding warmth across the 
entire floor area.As seen 
in Table 2, choose Model 
Numbers 240200WD and 
240020WD to end up with 
about 264 sq.ft. covered.
Table 1: 120 VAC Spo ols
Total Sq. ft. Total Sq. ft. Total Sq. ft. Wire 
Model  2” Spacing  2-1/2” Spacing  3” Spacing  Length  Amperage  Resistance
Number  15 watts/sq. ft. 12 watts/sq. ft. 10 watts/sq. ft. (ft.)  Draw  (ohms)
120010WD  8 10  12  47  1.0  112–137
120015WD  12  15  18  71  1.5  78–96
120020WD  16  20  24  94  2.0  58–72
120025WD  20  25  30  118  2.5  44–55
120030WD  24  30  36  141  3.0  34–42
120035WD  28  35  42  165  3.5  29-36
120040WD  32  40  48  188  4.0  25-32
120045WD  36  45  54  212  4.5  22–28
120050WD  40  50  60  235  5.0  20-26
120060WD  48  60  72  282  6.0  17-22
120070WD  56  70  84  329  7.0  14-19
120080WD  64  80  96  376  8.0  12–16
120090WD  72  90  108  423  9.0  11-15
120100WD  80  100  120  470  10.0 10-13
Table 2: 240 VAC Spo ols
Total Sq. ft. Total Sq. ft. Total Sq. ft. Wire 
Model  2” Spacing  2-1/2” Spacing  3” Spacing  Length  Amperage  Resistance
Number  15 watts/sq. ft. 12 watts/sq. ft. 10 watts/sq. ft. (ft.)  Draw  (ohms)
240020WD  16  20  24  94  1.0  223-274
240030WD  24  30  36  142  1.5  155-191
240040WD  32  40  48  188  2.0  116-143
240050WD  40  50  60  236  2.5  88-109
240060WD  48  60  72  282  3.0  68-84
240070WD  56  70  84  330  3.5  58-72
240080WD  64  80  96  376  4.0  51-63
240090WD  72  90  108  424  4.5  45-56
240100WD  80  100  120  470  5.0  41-51
240120WD  96  120  144  564  6.0  34-42
240140WD  112  140  168  658  7.0  29-36
240160WD  128  160  192  752  8.0  25-32
240180WD  144  180  216  846  9.0  22-28
240200WD  160  200  240  940  10.0 20-26
NEVER use 1”
spacing
NEVER use less than 2”spacing.
NO!
Note:  Models ending -J on the UL tag have an additional jacket over the heating cable.
Note:  Models ending -J on the UL tag have an additional jacket over the heating cable.
ALWAYS!