Manual

SunTouch WarmWire  Installation Manual  7
Phase  4: Electrical Rough-in
See wiring diagrams in Appendix 2 for different voltages and applications.
For additional help see www.suntouch.com.
New Construction (see below for existing construction)
OVERVIEW  We recommend the floor-warming system be installed on a 
dedicated circuit coming directly from the circuit breaker panel. Follow all 
National Electric Code (NEC) and other local electrical code requirements 
when installing this system. Work should be done with great care and with 
the power  turned off to the circuit being worked on.
STEP 4.1  Install a maximum 20-amp circuit breaker(s) into the breaker 
panel, depending on the load of the system.Use a 120-VAC single-p ole 
breaker for a 120-VAC system.Use a 240-VAC double-pole breaker for a 240-
VAC system. Use a Ground Fault Circuit Interrupter (GFCI) type if not using 
our controls (which have a built-in GFCI).
For systems that are too large to directly power through one SunStat 
but must be operated by one floor-sensing control,use a SunStat control 
in combination with up  to 10 SunStat Relay Controls.Contact a SunTouch 
dealer or the factory for more information.
STEP 4.2 Install an electrical box for the control.If installing one to two 
cables,use an extra-deep single-gang box to allow plenty of room for the 
wiring.Use a 4”-square box if installing three cables. The box can be located 
almost anywhere that is well ventilated. However,the best place is in the 
same room as the cable, typically about 60”above the floor,and within 
reach of the power lead wires of the cable.If  installing more than three 
cables,it will be necessary to connect their  p ower leads in a junction box 
first (see Step 4.4)  to keep from overfilling the control electrical box. Then 
route one power supply from this junction box  to the control box.
    See Step 5.23 for special requirements if the control will connec t to a 
heating cable entering a shower area.
STEP 4.3 Following code,feed 14- or 12-gauge NM type electrical wiring 
from the circuit breaker panel to the control electrical box.Leave about 
6”–8” of extra wire extended from the box to work with.
STEP 4.4  If the control box must be  mounted in a location that is too far 
to reach with the power lead wires,it will be necessary to mount a junction 
box where the lead wires can be terminated. Use a standard  junction box 
with a cover, mounting it below the floor, in the attic,or in another easily 
accessible location. It must remain easily accessible and not located behind 
a wall,cabinet,or similar obstruction. Then use 14- or 12-gauge NM type or 
other accepted electrical wiring to connect from the junction box to the 
control box.
STEP 4.5 Drill two 1/2” holes in the baseplate directly below the control 
electrical box. Then,as close to the  flo or surface as possible, drill two  
horizontal holes, intersecting the top holes.
STEP 4.6 If conduit is required by local electrical code, cut a length  of 
1/2” to 3/4” electrical conduit to run from the control box down to the base-
plate.At the baseplate it may be necessary  to chisel out more of the wood 
to make it easier to feed the wires up through the conduit.
STEP 4.7   Mark the circuit breaker in the panel which feeds the system 
with “Floor warming/bath or  similar description.
Existing Construction
OVERVIEW  It is recommended that the system be installed on a separate,
dedicated circuit coming directly from the breaker panel.In existing con-
struction, however, it  may be difficult to do this depending on the location 
of wiring and the breaker panel. Tapping off an existing circuit may be pos-
sible,but only if there is enough load capacity  to handle both the system 
and any additional loads that may be placed on the circuit.Keep in mind 
that typical hair dryers can pull up to 10 amps (1200 watts) of load.
Follow all NEC and other local electrical code requirements when install-
ing this system. Work should be done with great c are and with the power 
turned off to the circuit being  worked on.
STEP 4.2
Install an extra-deep single-gang 
box if connecting one or two cables 
to the control. Use a 4”-square deep 
box with a single-gang mud ring 
cover if connecting three cables,
because the extra room is needed 
for the wire,wire nuts,and control.
STEP 4.5