Manual

8 SunTouch WarmWire Installation Manual
STEP 4.8  Install a maximum 20-amp circuit breaker(s) into the breaker 
panel, depending on the load of the system.Use a 120-VAC single-p ole 
breaker for a 120-VAC system.Use a 240-VAC double-pole breaker for a 
240-VAC system. Use a Ground Fault Circuit Interrupter (GFCI) type if 
not using one of our controls (which have a built-in GFCI).
For systems that are too large to directly power through one SunStat 
but must be operated by one floor-sensing control,use a SunStat 
Control in combination with up to 10 SunStat Relay Controls.Contact a 
SunTouch dealer or the factory for more information.
STEP 4.9   Cut an opening in the wall for the control electrical box.
If installing one to two cables, use  an extra-deep single-gang box to 
allow plenty of room for the wiring. Use a 4”-square box if installing 
three cables. The box can be located almost anywhere that is well venti-
lated. However,the best place is in the same room as the cable,typically 
about 60” above the flo or,and within reach of the power lead wires of 
the cable. If installing more than three cables, it will be necessary to 
connect  their power leads in a junction box first (see Step 4.11) to k eep 
from overfilling the control b ox. Then route one power supply from this 
junction box to the control box. See Step 5.23 for special requirements 
if the control will connect to a heating cable entering a shower area.
STEP 4.10  Following code, feed 14- or 12-gauge NM type electrical 
wiring from the circuit breaker panel  to the control electrical box  
opening.Leave about 6”–8”of extra wire extended  from the opening.
STEP 4.11  If the control box must be mounted in a location that is 
too far to reach with the power lead wires,it will also be necessary to 
mount a junction box where the lead wires can terminate. Use a 
standard junc tion box with a cover,mounting it below the floor,in 
the attic, or in another easily accessible location. It must remain easily 
accessible and not located behind a cabinet or similar obstruction.Then 
use 14- or 12-gauge NM type or other accepted electrical wiring to con-
nect from the junction box to the control electrical box.
STEP 4.12  At the floor level below the control box, cut a 2”x 2”-wide 
piece from the wall surface.Use a wood chisel to notch out a channel in 
the baseplate to make it easier to route the wires up the wall.
STEP 4.13  Mark the circuit breaker in the panel which feeds the 
system with “Floor warming/bath or similar.
Phase  5: Install the Cables
Getting Started
IMPORTANT!   Refer to Phase 8 and Appendix 1 to make sure the 
floor is properly prepared for  installation of the cable(s), especially 
the use of reinforcement,leveling,and insulation on concrete slab.
STEP 5.1  Use the sketch and design considerations made  earlier in 
Phase 1 to begin  laying the cables. Do not install the cables closer  
than about 6” from wax toilet rings and plumbing to keep from over-
heating these items.
STEP 5.2   Make sure to space the cables to provide the warmth 
desired.NE VERspace them at 1”apart because this will cause a very 
hot area and may damage the system. Before installing the cables, make 
certain the proper cable length  and voltage has been selected for the 
square footage to be heated .
STEP 5.3  If this is new construction, draw lines on the floor or use tem-
plates to outline the area of any cabinets, fixtures,or future  walls that 
will be placed in the room.  NEVER install the cables  under cabinets,fix-
tures,or walls.  Excess heat may 
build up under these items and 
cause damage.
STEP 5.4  Decide which direc-
tion the cables will run on the 
floor for the easiest coverage.
Refer to the sample layouts 
in this manual for assistance.
Depending  on the shape of the 
area, it may help to think of it in 
terms of several smaller areas.
NEVER cross the cables over each other or cut them shorter. Damage 
STEP 4.10
STEP 4.12
STEP 5.3
STEP 4.11
STEP 4.9
NEVER use 1”
spacing
NEVER use less than 2”spacing.
NO!